Add to Cart
~Kaixiang company is in leading position in generator set testing
and maintenance industry, besides general functions, its load bank
has following unique advantages:
1. Standard Testing Function: System can do stable test, transient
test, and realize functions, such as setting, fluctuation, instant
load, and instant unload.
2. Super Power Load: high load power density, large capacity of
single set, parallel running to finish super power testing, and
realize tens of megawatts of power loading.
3. Accurate Data: with high precision data collection module and
measuring meter, related equipment has passed the certification by
CMA (China Metrology Accreditation) qualification testing
institution, and ensure the reliability of data.
4. Flexible Control Mode: based on different using habit, several
control mode as following can be choose, local panel operation,
remote box controlling, and intelligent software.
5. Intelligent Load: after setting generator rated power in
software, system realize rapid loading through preset proportion,
automatically and continuously load multiple power value and common
tests, like stepping, full load, and over load, so that improve
working efficiency.
6. High Efficiency Data Management: display real-time testing data,
generate form, curve graph or report automatically, also can put
data into storage. According to generator set No. set up testing
file, support to query at any time, and improve data management
efficiency.
7. Comprehensive Protection Function: multiple protection, like
over temperature, smoke. When in danger, automatically terminate
the test and give alarm to protect safety of personnel and
equipment.
8. Stable Running: with the latest generation control module as the
core, a sharp rise in system response speed and anti-interference
performance, avoid function failure in complex electrical
environment, and ensure system running stably and reliably.
9. New Load Bank Technology: using the international advanced AC
load bank technology, overcome the old water bank defects, such as
bear bumpy, unable to use when go to sea, realize Mooring Trial and
Sea Trail, and simulate the real working condition of generator
running.
10. Mature Manufacturing Technology: load element using excellent
anti-corrosion materials, waterproof insulation container
packaging, suitable for adverse environment such as ocean. Internal
layout is reasonable, air channel is clear, rapid heat emission,
and satisfy continuous working need.
Technical Specifications:
Technical Parameter
Input Voltage
4160VAC, 3 Phase, 60Hz or 3800VAC, 3 Phase, 50 Hz
Max Load Power
Apparent Power: 1415kVA
Resistive Load: 1200kW
Inductive Load: 750kvar
Load Resolution
When voltage is 4160VAC,3phase,60HZ
Resistive Load: 5 steps,50,100,200,400,450kW
Inductive Load: 5 steps, 37.5,75,150,187.5,300kvar
When voltage is 3800V,3phase,50ZH
Resistive Load: 5 steps,41.67,83.33,166.67,333.33,375kW
Inductive Load: 5 steps, 37.5,75,150,187.5,300kvar
Power Factor
0.8
Load Tolerance (each step)
±5%
Load Tolerance (overall)
±3%
Working Power
External :480VAC, 3 Phase, 50/60 Hz
Internal: 4160VAC, 3 Phase, 60Hz or 3800VAC, 3 Phase, 50 Hz
Wire Connection
Load bank input——Copper bar (star coupling ”Y”)
Control power input——Connector-bar
Communication Interface
RS485,RS232
Insulation
F
Max Protection Grade
IP54
Way of Working
Continuous Working
Cooling
Forced air cooling, horizontal inlet air, vertical exhaust cooling
Enclosure
Container type,with a ladder, air inlet and outlet with mesh
enclosure and protection door
Transportation
Hoisting, there are lifting lug in top of casing
Color
RAL7032
Dimensions
About 6058mm*2438mm*2591mm(L×W×H)
Weight
About 10000kg