210kn Standard Disc Transmission Line Tool Suspension Toughened Glass Insulators

Brand Name:Boyu
Certification:ISO9001
Model Number:BYLXY3-210
Minimum Order Quantity:500 sets
Delivery Time:25-30days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Supplier`s last login times: within 26 hours
Product Details Company Profile
Product Details

Transmission Line Stringing Tools 210kn Standard Disc Anti-fouling Suspension Toughened Glass Insulators


Feature

  1. Good pollution resistance
  2. Good structural stability
  3. Aging resistance
  4. High line operation efficiency
  5. Light weight
  6. Excellent mechanical properties
  7. Excellent electrical corrosion resistance

Product parameters

ModelBYLXY-70BYLXY1-70BYLXY-100BYLXY-120BYLXY3-160BYLXY3-210BYLXY-240BYLXY-300

Mechanical damage load≥

KN

7070100120160210240300

Battering load≥

KN

5655656786781017101710171017

Electromechanical load test value/h

KN

52.552.57590120157.5180225

Nominal Height H

mm

127146146146155170170195

Nominal diameter of insulator D

mm

255255255255280280280320

Minimum nominal creepage distance

mm

320320320320380390390485

Peak voltage tolerance for lightning full - wave shock

kv

≥100≥100≥100≥100≥105≥105≥105≥105

Effective value of power frequency voltage≥

kv

1min wet resistance4040404042424245
Breakdown130130130130130130130130
Weight/set (kg)3.773.784.14.26.26.76.810.7
  1. Insulators are a special type of insulation control that can play an important role in overhead transmission lines.
  2. Initially, insulators were mostly used in utility poles. Later, one end of the high-voltage high-voltage wire connection tower was hung with a number of disk-shaped insulators. This is to increase the creepage distance, usually made of glass or ceramic, called insulators.
  3. Due to the high mechanical strength of the surface layer of the glass insulator, cracks are less likely to occur on the surface. The electrical strength of the glass generally remains constant throughout the run and its aging process is much slower than porcelain.
  4. The insulator will not fail due to various electromechanical stresses caused by changes in environmental and electrical load conditions, otherwise the insulator will not have a significant effect, which will damage the use and operating life of the entire line.​

China 210kn Standard Disc Transmission Line Tool Suspension Toughened Glass Insulators supplier

210kn Standard Disc Transmission Line Tool Suspension Toughened Glass Insulators

Inquiry Cart 0