Home /Diesel Generators /

50 Hz Perkins Diesel Generator , LL7024P , 1800rpm , Three Phase

50 Hz Perkins Diesel Generator , LL7024P , 1800rpm , Three Phase

Brand Name:GSKA
Model Number:JP-P900E1
Minimum Order Quantity:20-30 pieces
Delivery Time:3-5 days on receipt of official sales contract
Payment Terms:L/C,D/P,D/A, Alipay, West Union, TT. Cash,Paypal
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Dongguan Guangdong China
Address: No. 2, Shajiao Sijia Gate, Humen Town, Dongguan City, Guangdong Province, China
Supplier`s last login times: within 48 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details


1, Engine Make & Model: Perkins 4006TAG3A

2,Generating Set Model: P900E1

3,Alternator Model: LL7024P

4, Circuit Breaker Type: 3 Pole ACB/MCCB

5, Frequency: 50 Hz / 60 Hz

6,Cycle: 4 Stroke

7, Engine Speed: 1500rpm/1800rpm

8, Cooling Method: Turbo, Water/Air cooling

9, Governing Type: Electronic

10, Output Type: AC Three Phase

10, No.of Cylinders/Alignment: 6 / In Line

11,Base Frame Type: Heavy Duty FabriCAT-parts-partsed Steel


LL7024P 50 Hz Perkins Diesel Generator , 4006TAG3A

Output Ratings

Generating Set Model

* P900E1

Prime* Standby*

380-415V, 50 Hz

800.0 kVA 900.0 kVA

640.0 kW 720.0 kW

480V, 60 Hz

844.0 kVA 938.0 kVA

675.2 kW 750.4 kW

  • Refer to ratings definitions on page 4.

Ratings at 0.8 power factor.


Technical Data

Engine Make & Model:

Perkins 4006TAG3A

Alternator Model:

LL7024P

Base Frame Type:

Heavy Duty FabriCAT-parts-partsed Steel

Circuit Breaker Type:

3 Pole ACB/MCCB

Frequency:

50 Hz 60 Hz

Engine Speed: RPM

1500 1800

Fuel Tank Capacity: litres (US gal)

1494 (394.7)

Fuel Consumption: P800P1 l/hr (US gal/hr)

163.0 (43.1) 188.3 (49.7)

Fuel Consumption: P900E1 l/hr (US gal/hr)

183.5 (48.5) 211.9 (56.0)

P800P1 / P900E1


Engine Technical Data


Physical Data


Manufacturer: Perkins

Model: 4006TAG3A

No. of Cylinders/Alignment: 6 / In Line

Cycle: 4 Stroke

Induction: Turbocharged Air To Air Charge Cooled

Cooling Method: Water

Governing Type: Electronic

Governing Class: ISO 8528 G2

Compression Ratio: 13.6:1

Displacement: l (cu.in) 22.9 (1398.7)

Bore/Stroke: mm (in) 160.0 (6.3)/190.0 (7.5)

Moment of Inertia: kg m² (lb. in²) 10.61 (36256)

Engine Electrical System:

-Voltage/Ground: 24/Negative

-Battery Charger Amps: 40

Weight: kg (lb) - Dry: 2524 (5564)

- Wet: 2663 (5871)


Air System 50 Hz 60 Hz


Air Filter Type: Replaceable

Element Combustion Air Flow:m³/min (cfm)

-Standby: 73.0 (2578) 78.0 (2755)

-Prime: 69.0 (2437) 76.0 (2684)

Max. Combustion Air Intake Restriction: kPa (in H2O) 3.7 (14.9) 3.7 (14.9)

Radiator Cooling Air Flow: m³/min (cfm) 1134.0 (40047) 1326.0 (46827)

External Restriction to Cooling Air Flow: Pa (in H2O) 250 (1.0) 250 (1.0)


Cooling System 50 Hz 60 Hz


Cooling System Capacity:l (US gal) 105.0 (27.7) 105.0 (27.7)

Water Pump Type: Centrifugal

Heat Rejected to Water & Lube Oil: kW (Btu/min)

-Standby: 300.0 (17061) 320.0 (18198)

-Prime: 270.0 (15355) 290.0 (16492)

Heat Radiation to Room:kW (Btu/min)

-Standby: 97.1 (5522) 106.0 (6028)

-Prime: 91.1 (5181) 100.0 (5687)

Radiator Fan Load: kW (hp) 26.0 (34.9) 44.0 (59.0)

Cooling system designed to operate in ambient conditions up to 50°C (122°F).


Performance 50 Hz 60 Hz

Engine Speed: RPM 1500 1800

Gross Engine Power: kW (hp)

-Standby: 786.0 (1054.0) 839.0 (1125.0)

-Prime: 705.0 (945.0) 759.0 (1018.0)

BMEP: kPa (psi)

-Standby: 2743.0 (397.9) 2440.0 (353.9)

-Prime: 2461.0 (356.9) 2208.0 (320.2)

Regenerative Power: kW 70.0 75.0


LubriCAT-parts-partsion System

Oil Filter Type: Spin-On, Full Flow

Total Oil Capacity l (US gal): 123.0 (32.5)

Oil Pan l (US gal): 113.4 (30.0)

Oil Type: API CG4 15W-40

Cooling Method: Water


Fuel System

Fuel Filter Type: Replaceable

Element Recommended Fuel: Class A2 Diesel

Fuel Consumption: l/hr (US gal/hr)


110% 100% 75% 50%

Load Load Load Load

P800P1

50 Hz 179.4 (47.4) 163.0 (43.1) 123.6 (32.7) 88.2 (23.3)

60 Hz 211.9 (56.0) 188.3 (49.7) 138.9 (36.7) 96.3 (25.4)

P900E1

50 Hz 183.5 (48.5) 137.9 (36.4) 96.8 (25.6)

60 Hz 211.9 (56.0) 154.6 (40.8) 105.1 (27.8)

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)


Exhaust System 50 Hz 60 Hz

Silencer Type: Level 1

Silencer Model & Qty: SD250 (1) Pressure Drop Across

Silencer System: kPa (in Hg) 1.35 (0.399) 0.34 (0.100)

Silencer Noise Reduction

Level: dB 20 16

Max. Allowable Back

Pressure: kPa (in. Hg) 7.0 (2.1) 7.0 (2.1)

Exhaust Gas Flow:

m³/min (cfm)

-Standby: 193.0 (6816) 209.0 (7381)

-Prime: 193.0 (6816) 209.0 (7381)

Exhaust Gas Temperature: °C (°F)

m³/min (cfm)

-Standby: 500 (932) 500 (932)

-Prime: 500 (932) 500 (932)

P800P1 / P900E1


Alternator Performance Data

Data Item

50 Hz 60 Hz

415/240V

400/230V

380/220V

480/277V

380/220V

440/254V


Motor Starting Capability* kVA


2613


2446


2228


2879


1885


2464

Short Circuit Capacity** %

300

300

300

300

300

300

Reactances: Per Unit

Xd X'd X''d

2.570


0.120


0.098

2.770


0.130


0.105

3.060


0.140


0.116

2.430


0.110


0.092

3.840


0.180


0.146

2.890


0.140


0.110

Reactances shown are applicable to prime ratings

  • Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.

** With optional Permanent Magnet generator or AREP excitation.


Alternator Technical Data

Physical Data Operating Data

Manufacturer: FG WILSON

Overspeed: RPM 2250

Model: LL7024P

Voltage Regulation (steady state) (%): + /- 0.5

No. of Bearings: 1

Wave Form NEMA = TIF: 50

Insulation Class: H

Wave Form IEC = THF: 2.0%

Winding Pitch Code: 2/3 - 6S

Total Harmonic Content LL/LN: 4.0%

Wires: 6

Supression is in line with European Standard Radio Interference: EN61000-6

Ingress Protection Rating: IP23

Radiant Heat: kW (Btu/min)

-50 Hz: 37.1 (2110)

-60 Hz: 42.0 (2388)

Excitation System: AREP

AVR Model: R448

P800P1 / P900E1


Technical Data

3 Phase Ratings and Performance at 50 Hz, 1500 RPM

3 Phase Ratings and Performance at 60 Hz, 1800 RPM


Voltage Prime Model Standby Model Voltage Prime Model Standby Model

P800P1 P900E1 P800P1 P900E1


kVA kW

kVA kW


kVA kW

kVA kW

415/240V

800.0 640.0

900.0 720.0

480/277V

844.0 675.2

938.0 750.4

400/230V

800.0 640.0

900.0 720.0




380/220V

800.0 640.0

900.0 720.0

380/220V

835.0 668.0

920.0 736.0




440/254V

- -

- -


Definitions

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).


Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.


Standard Reference Conditions

Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.



Weights and Dimensions


Weights: kg (lb) Dimensions: mm (in)


Net (+ lube oil)


6259 (13799)


Length


4280 (168.5)

Wet (+ lube oil & coolant)

6370 (14043)

Width

1912 (75.3)

Fuel, lube oil & coolant

6530 (14396)

Height

2277 (89.6)

General Data


Documents

A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.


Generating Set Standards

The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.


Warranty

All equipment carries full manufacturer's warranty.



China 50 Hz Perkins Diesel Generator , LL7024P , 1800rpm , Three Phase supplier

50 Hz Perkins Diesel Generator , LL7024P , 1800rpm , Three Phase

Inquiry Cart 0