Household Uninterruptible Power Supply UPS220V Output Tower
Matters needing attention:
Because of the particularity of its inverter and battery work, the
installation and use of UPS power supply must have a set of strict
and scientific operating procedures, in order to improve the
stability of work, reduce the failure rate of equipment, and truly
achieve uninterrupted power supply of equipment.
(1) The installation environment of the UPS power supply should be
protected from direct sunlight and have enough ventilation space to
ensure that the operating temperature is not higher than 25 ° C. If
the operating temperature exceeds 25 ° C, the battery life is
reduced by about half for every 10 ° C increase in temperature
rise.
(2) It is not suitable to use high-power thyristor load, thyristor
bridge rectifier or half-wave rectifier load at the output end of
the UPS power supply, which is easy to cause the inverter's final
drive transistor to be burned.
(3) Strictly follow the correct startup and shutdown sequence to
avoid large fluctuations in the voltage output of the UPS power
supply when the load suddenly increases or decreases, so that the
UPS power supply cannot work normally.
(4) Do not frequently turn off or on the UPS power supply.
Generally, wait at least 30 seconds after turning off the UPS power
supply. The cause of frequent UPS power failures is that users
start or shut down frequently, and the UPS power supply switches
between inverter power supply and bypass power supply with load.
(5) Practice has proved that for the vast majority of UPS power
supplies, it is the best working mode to control the load within
the range of 50%~60% rated output power. It is forbidden to use
over load. The manufacturer suggests that the maximum starting load
of UPS power supply should be controlled within 80%. If overload is
used, it will often breakdown the inverter triode in the inverter
state. Not too light load operation, this situation is easy to
cause battery failure because the battery discharge current is too
small.
(6) Regularly maintain the UPS power supply: observe the status of
the working indiCAT-parts-partsor, remove dust, measure the voltage
of the battery, replace the unqualified battery, check the running
status of the fan, and detect and adjust the system parameters of
the UPS.
(7) UPS power supply is more suitable for with micro capacitive
load, not suitable for charged inductive load, such as air
conditioning, motor, electric drill, fan, etc. If the UPS power
load is resistive or inductive, reduce the load to avoid overload.
Model | GSKA-500 | GSKA-800 | GSKA-1000 | GSKA-1500 | GSKA-2000 | GSKA-2500 | GSKA-3000 | GSKA-5000 | |
Rated Capacity | 500VA | 800VA | 1000VA | 1500VA | 2000VA | 2500VA | 3000VA | 5000VA | |
Rated Power | 300W | 500W | 700W | 1050W | 1400W | 1800W | 2100W | 3500W | |
Transformer | Toroidal transformer | ||||||||
Interface | LED graphic | ||||||||
Display status | working&loading&battery | ||||||||
Working mode | PV(Photovoltaic priority)/AC(AC priority) optional | ||||||||
Input | Voltage | 140-275Vac | |||||||
Frequency | 45-65Hz | ||||||||
Output | Voltage | 220Vac±3% for inveter; 195v-240V for avr | |||||||
Frequency | 50/60Hz ± 0.3Hz, subject to the main | ||||||||
Wave Form | Pure sine wave | ||||||||
Wave Distortion | ≤3% | ||||||||
Protection | overload/high temperature/output high voltage /output low voltage/ battery low voltage shortcircuit/over-charge/over-discharge/reversed polarity(optional) | ||||||||
Transfer Time | ≤4ms | ||||||||
Battery Voltage | 12VDC | 24VDC | 48VDC | ||||||
Charge Voltage | 13.6V±0.3V | 27.2V±0.6V | 54.5V±1V | ||||||
Low Battery Voltage Limit | 10.9V±0.3V | 21.8V±0.5V | 42V±1V | ||||||
Protections Battery Low Voltage Protection Point | 10.2V±0.3V | 20.5V+0.5V | 41V±1V | ||||||
Charge Current | Max.10A/15A/20A optional | ||||||||
Environmental | Operating Temperature | 0~40℃ | |||||||
Relative Humidity | 10%~90%RH,non-condensing | ||||||||
Storage Temperature | -15-45℃ | ||||||||
Packing | Machine Size(mm) | 280x144x213 | 385x190x320 | ||||||
Qty/Ctn | 4 | 4 | 2 | 2 | 1 | 1 | 1 | 1 | |
Carton Size(mm) | 785x305x240 | 415x410x245 | 410x290x320 | ||||||
CartonG.W.(kg) | 22 | 26 | 17.2 | 19.1 | 410x290x321 |