Add to Cart
Elite Power Series Online HF UPS 10-20KVA 3 / 1phase For Telecommunication
Quick Detail:
Elite Power Series Online HF UPS 10-20KVA 3 / 1phase
1)Type: On-line
2)Phase:3/1Phase, 4Wires +G
3) Features: PFC technology, AC and cold start
Introduction
Elite Power series Online HF UPS 10-20kva is completely digital control UPS with advanced PFC technology. It’s designed to satisfy high end requirement.
Main Featurs:
Technical Specification:
Model | EP310S | EP310L | EP315L | EP320L | ||||||||
Capacity | 10kVA/8kW | 10kVA/8kW | 15KVA/12kW | 20KVA/16kW | ||||||||
Input | Phase | 3/1Phase, 4Wires +G | ||||||||||
Power Factor | Above0.99 | |||||||||||
THDi | Less than 6%(100% non-linear load) | |||||||||||
Voltage | 300-480Vac | |||||||||||
Frequency | 40-70hz | |||||||||||
Bypass Voltage Range | ±15%(Optional ±10%, ±25%) Frequency protection range: ±10% | |||||||||||
ECO Range | Same as bypass | |||||||||||
Output | Voltage Precision | 220/230Vac±1% | ||||||||||
Phase | Single Phase | |||||||||||
Power Factor | 0.8(lag) | |||||||||||
Frequency | 50/60 ±4Hz (Line mode), 50/60±0.1Hz ( Battery mode) | |||||||||||
Crest Factor | 3:1 | |||||||||||
THDv | <2%(linear load) | |||||||||||
Overload | 105%<load<125% for 1 mins , 125%<load<150% for 30sec | |||||||||||
Transfer time | 0ms(Between AC to Battery mode) | |||||||||||
0ms(Inverter to Bypass mode) | ||||||||||||
Battery | DC voltage | 240VDC or 192VDC (Convertible via jumper) | ||||||||||
Configuration | 20*12V/9AH | External Battery Bank | ||||||||||
Backup Time(full load) | 3Min | Depends on the external battery capacity | ||||||||||
Backup Time (half load) | 8Min | |||||||||||
Recharging current | 1A | 5A | ||||||||||
Battery type | Lead-acid Maintenance-free battery | |||||||||||
Recharge Time | 90% capacity after 8hours | |||||||||||
Communication Interface | RS232, Dry Contact, Optional(SNMP CARD, RS485, Parallel card) | |||||||||||
LCD Indication |
output voltage/frequency/load watt/VA value and percent, intverer/PFC temperature, Bus voltage, charger voltage/ status”on “or “off”;
| |||||||||||
LED Indication | 1.Green LED for normal, 2.Yellow for battery, 3.Red for fault | |||||||||||
Noise | <55dB | |||||||||||
System efficiency | ECO mode ≥98%, Nomal mode ≥90% | |||||||||||
Operating Environment | Temp. | 0℃-40℃ | ||||||||||
Humidity | 0-95%non condensing | |||||||||||
Storage Temp. | -25℃-55℃ | |||||||||||
Altitude | <1500m | |||||||||||
Add function | 1.History Logger function (standard) 2.Back Up time display function (standard) | |||||||||||
Other | Unit Dimension (W* H * D mm) | 290*642*600 | 300*735*600 | |||||||||
Packing | 390*810*700 | 420*920*720 | ||||||||||
Weight (kg) | 90 | 40 | 45 | 45 |