Introduction:


This PWR series Rack mount 3phase UPS10~40KVA is online double conversion online UPS with fully DSP controlled technology.It’s convertable 3/3phase or 3/1phase with high effiecny compact design,an ideal choice for small and medium data center.


Perfect Applications

Small and medium data center, network servers and workstation, control system, communication system, office, PC etc

Characteristics

  • Mounted in 19 inch rack, or install as tower UPS with standing support.
  • 5.5-inch touch LCD, with IoT functions.
  • Cold start function with battery only
  • Flexible configuration as 3/3, 3/1
  • High power density, and high efficency to save energy.
  • Advanced ABM and power walk-in function, greatly extending battery lifespan.

ModelPWR3310PWR3315PWR3320PWR3320PWR3340
Rate Power10kVA/10kW15kVA/15kW20kVA/20kW30kVA/30kW40kVA/40kW
Main inputInput3P5W (3P+N+PE)
Rate Voltage380/400/415VAC(L-L);220/230/240VAC(L-N)
Rate Freq.50/60Hz
Input PF>0.99
Current distortionTHDi<3%(100% Linear load)
Voltage range304~478VAC(L-L)full load;304~228VAC (L-L) power derate from 100% to 75%
Freq. range40-70Hz
BatteryRate voltage±240VDC(32-44 batteries settable)
Charging capacity20%*Pout
Charging accuracy±1%
BypassRate voltage380/400/415VAC(L-L)220/230/240VAC(L-N)
Voltage rangeRange: -40%- +25% , Settable, default -20%~+15%
Frequency range50/60Hz,Settable:±1Hz,±3Hz,±5Hz
InverterRate voltage380/400/415VAC(L-L);220/230/240VAC(L-N)
Rate Freq.50/60Hz
Output PF1
Voltage accuracy±1.0%
Load response<5% (20% - 80% -20% step load)
Recovery time< 20ms (0% - 100% -0% step load)
Output THDu<1%(linear load),<5% (non-linear load according to IEC 62040-3)
Overload110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms
Frequency accuracy0.1%
Synchronize windowSettable,±0.5Hz-±5Hz,default ±3Hz
Slew rateSettable,0.5Hz/S-3Hz/S,default 0.5Hz/S
Crest factor3:1
Phase Accuracy120°±0.5°
SystemEfficiencyNormal Mode≥96%;Battery Mode≥96%
DisplayLED + 5.5 inch touch LCD
Certification- SafetyIEC62040-1, IEC60950-1
Certification- EMSIEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4 (EFT);IEC61000-4-5 (Surge)
IP degreeIP20
ConfigurationUSB, RS232, RS485, Dry contact
OptionSNMP card, AS400 card, Parallel kit, LBS, Air filter, Cold start
Environment0-40℃(operation);-25℃~70℃(storage);0-95% (Humidity, non-condensing )
Dimension (W*D*H) mm440*700*130*130 (3U)440*700*130*130 (3U)