IEC 61850-9-2 Transformer Auxiliary Relay for Mechanical protection recorder 1024

Brand Name:OEM
Minimum Order Quantity:10 pcs
Delivery Time:10days
Payment Terms:T/T
Place of Origin:China
Price:contact
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 27P , Block B , Duhui 100 , Zhonghang Road , Futian District , Shenzhen , China
Supplier`s last login times: within 9 hours
Product Details Company Profile
Product Details

IEC 61850-9-2 Transformer Auxiliary Relay for Mechanical protection recorder 1024


The PCS-974 relay provides mechanical protection for transformer tanks. The source of mechanical protection can be designed from non-electrical quantities, such as gas, oil temperature, winding temperature, pressure and oil level. It receives the mechanical inputs from transformer tank and issues the tripping or alarm command with or without time delay. The mechanical inputs employ the inputs with large pickup power instead of common binary inputs.


Protection and Monitoring
Mechanical protection (26: oil and winding temperature; 63: gas, pressure; 71: oil level; etc). Self diagnostic. Auxiliary power supervision. Event recorder including 1024 disturbance records, 1024 binary events, 1024 supervision events and 1024 operating logs.


Communication

Two 10Base-T/100Base-TX (RJ45) ports and two optional 100Base-FX ports with IEC 61850-8-1 MMS and GOOSE

for non-time-critical message, IEC 60870-5-103 over TCP/IP or DNP 3.0.
Two RS-485 rear ports with IEC 60870-5-103.
Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling Value and GOOSE for time-critical message.
One RS-485 rear port for clock synchronization.
One RS-232 rear port for printer.
1 faceplate RJ45 port for testing and setting.
Clock synchronization via Pulse-Per-Second, IRIG-B and SNTP.

China IEC 61850-9-2 Transformer Auxiliary Relay for Mechanical protection recorder 1024 supplier

IEC 61850-9-2 Transformer Auxiliary Relay for Mechanical protection recorder 1024

Inquiry Cart 0