General info
TypeDigital Output
Signal specification125 V d.c. / 250 V a.c., (5 - 125 V d.c. / 5 - 250 V a.c.), 2 A
Article number3BSE069055R1
Number of channels16
Signal typeRelay (NO)
HARTNo
SOENo
RedundancyNo
High integrityNo
Intrinsic safetyNo
MechanicsS800


Detailed data
IsolationIndividually isolated, channel-to-channel and to circuit common
Maximum field cable length600 meters (656 yards)
Rated insulation voltage250 V
Dielectric test voltage2000 V a.c.
Power dissipationTyp. 3.5 W
Current consumption +5 V Modulebus45 mA
Current consumption +24 V Modulebus80 mA
Current consumption +24 V external0


Environment and certification
CE markYes
Electrical safetyIEC 61131-2
Hazardous LocationC1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
Marine certificationDNV-GL
Protection ratingIP20 according to IEC 60529
Corrosive atmosphere ISA-S71.04G3
Climatic operating conditions0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2
Pollution degreeDegree 2, IEC 60664-1
Mechanical operating conditionsIEC/EN 61131-2
EMCEN 61000-6-4, EN 61000-6-2
Overvoltage categoriesIEC/EN 60664-1, EN 50178
Equipment classClass I according to IEC 61140; (earth protected)
Max ambient temperature55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F)
RoHS complianceEN 50581:2012
WEEE complianceDIRECTIVE/2012/19/EU

The DO828 is an 16 channel 125V d.c. / 250V a.c. relay output module for the S800 I/O. The maximum output voltage is 125V d.c. / 250V a.c. and the maximum continuous output current is 2A. All outputs are individually isolated.

Each output channel consists of optical isolation barrier, output state indication LED, relay driver, relay and EMC protection components.

The relay supply voltage supervision, derived from the 12 V distributed on the ModuleBus, gives an error signal if the voltage disappears, and the Warning LED turns on. The error signal can be read through the ModuleBus. This supervision can be enabled/disabled with a parameter.

Features and benefits

  • 16 channels for 125V d.c. / 250V a.c. relay outputs
  • 16 isolated channels
  • Output status indicators
  • OSP sets outputs to predetermined state uponerror detection