3 Phase True Double Conversion UPS , High Frequency data center ups Uninterrupted Power Supply

Brand Name:SOROTEC
Certification:CE,ROHS,ISO9000
Model Number:HP9335C Plus 10-30kVA Online UPS
Minimum Order Quantity:2PCS Online UPS
Delivery Time:Within 15-30days after receiving your 30% TT deposit
Payment Terms:L/C, , T/T, Western Union
Contact Now

Add to Cart

Active Member
Location: Shenzhen Guangdong
Address: Building B22 , Tantou West Industrial Park , Songgang Town , Bao'an District ,Shenzhen ,518105 P.R.CHINA
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

3 Phase True Double Conversion UPS , High Frequency data center ups Uninterrupted Power Supply


HP9335C PLUS Series High Frequency Online UPS represents the best solution that is both cost effective and environmental friendly,it delivers an excellent integrated autonomy,reduced footprint and optimum input and output performances,guaranteeing reliable and flexible power.


Key Features:

  • Output power factor 0.9
  • True double online conversion
  • Optional N+X parallel redundancy
  • Generator Input Available
  • Support dual-mains inputs
  • Battery numbers adjustable
  • Maintenance bypass available
  • 50Hz/60Hz frequency can convertion
  • ECO mode operation for energy saving
  • Emergency power off function (EPO)
  • Wide input voltage range (110-300 VAC)
  • Active power factor correction in all phases
  • DSP technology guarantees high performance
  • SNMP+USB+RS-232 multiple communications
  • Optional isolation transformer offers full isolation
  • 3-stage extendable charging design for optimized battery performance

Technical Parameters of High Frequency Online UPS

MODELHP9335C Plus 10-30KVA
10K10K-XL15K15K-XL20K20K-XL30K30K-XL
CAPACITY10KVA / 9KW15KVA / 13.5KW20KVA / 18KW30KVA / 27KW
PHASE3 Phase with Neutral
INPUT
Voltage RangeLow Line Loss110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load
Low Line ComebackLow Line Loss Voltage + 10V
High Line Loss300 VAC(Ph-N) ± 3 %
High Line ComebackHigh Line Loss Voltage - 10V
PhaseThree phase with ground
Power Factor≥ 0.99 at 100% Load
OUTPUT
Output voltage208/220/230/240VAC(Ph-N)
AC Voltage Regulation± 1%
Frequency Range (Synchronized Range)46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
OverloadAC mode100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec
Battery mode100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
Current Crest Ratio3:1 max
Harmonic Distortion≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load
Transfer TimeLine←→Battery0 ms
Inverte←→Bypass0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Line←→ECO<10 ms
EFFICIENCY
AC mode> 89%> 89%> 89%> 90%
Battery Mode> 86%> 88%> 87%> 89%
BATTERY
Standard ModelType






12 V / 9 Ah12 V / 9 Ah12 V / 9 Ah12 V / 9 Ah
Numbers20(18-20 adjustable)2 x 20(18-20 adjustable)2 x 20(18-20 adjustable)3 x 20(18-20 adjustable)
Recharge Time9 hours recover to 90% capacity
Charging Current1.0 A ± 10% (max.)2.0 A ± 10% (max.)2.0 A ± 10% (max.)4.0 A ± 10% (max.)
Charging Voltage273 VDC ± 1%
Long-run ModelTypeDepending on applications
Numbers18-20
Charging Current4.0 A ± 10% (max.)4.0 A ± 10% (max.)4.0 A ± 10% (max.)12.0 A ± 10% (max.)
Charging Voltage273 VDC ± 1%
PHYSICAL
Standard ModelDimension,DxWxH(mm)832 X250X894832 X250X1275
Long-run ModelDimension,DxWxH(mm)609 X250X768832 X250X828
ENVIRONMENT
Operation Temperature0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity<95 % and non-condensing
Operation Altitude<1000m
Acoustic Noise LevelLess than 58dB @ 1 MeterLess than 60dB @ 1 Meter
MANAGEMENT
Smart RS-232 / USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
USBPower management from SNMP manager and web browser