Add to Cart
Parallel Bunched Aerial Insulated Cable
■ Product standard
Enterprise standard , Refer to“Chosen and used technical condition of parallel clustered aerial insulation cable” issued by Department of Agricultural Work , State Electric Power Corporation.
■ Application
The parallel clustered aerial insulation cable with 0.6/1kV rated voltage and below can be wide used for low voltage electric distribution system at country .This cable features good weather ability , anti-ageing , less wire loss , simple in construction , short time limit for project and can prevent effectively from electric larceny and creepage , etc phenomenon and has better safe property.
■ Operating characteristics
1. Rated voltage U0/U: 0.6/1kv
2. Max. permissible continuous temperature:
PVC,PE insulated aerial cables:70℃; XLPE insulated aerial cables:90℃
3. Max. short-circuit temperature of the conductor shall not exceed:
PVC insulated aerial cables:160℃; PE insulated aerial cables:130℃; XLPE insulated aerial cables:250℃.
4. The installation ambient temperature:
PE, XLPE≥-20℃; PVC≥0℃
■ Type of cable
Type | Name |
BS-JKV-0.6/1 | Rated voltage 0.6/1kV Copper-conductor , PVC insulated and Parallel bunched aerial insulated cable |
BS-JKLV-0.6/1 | Rated voltage 0.6/1kV Aluminum-conductor , PVC insulated and Parallel bunched aerial insulated cable |
BS-JKY-0.6/1 | Rated voltage 0.6/1kV Copper-conductor , PE insulated and Parallel bunched aerial insulated cable |
BS-JKLY-0.6/1 | Rated voltage 0.6/1kV Aluminum-conductor , PE insulated and Parallel bunched aerial insulated cable |
BS-JKYJ-0.6/1 | Rated voltage 0.6/1kV Copper-conductor , XLPE insulated and Parallel bunched aerial insulated cable |
BS-JKLYJ-0.6/1 | Rated voltage 0.6/1kV Aluminum-conductor , XLPE insulated and Parallel bunched aerial insulated cable |
■ Production range of cable
Type | No. of cores | Rated Voltage kV | Nominal cross-sectional mm2 |
BS-JKV,BS-JKY, BS-JKYJ | 2 | 0.6/1 | 2.5~70 |
BS-JKLV,BS-JKLY, BS-JKLYJ | 4—120 | ||
BS-JKV,BS-JKY, BS-JKYJ | 4 | 2.5~70 | |
BS-JKLV,BS-JKLY, BS-JKLYJ | 4—70 | ||
BS-JKV,BS-JKY, BS-JKYJ | 3+1 | 6~120 | |
BS-JKLV,BS-JKLY, BS-JKLYJ | 6—120 |
■ Construction and main technical data
BS two-core constant section of parallel clustered aerial insulated cable | |||||||||||||||||
Number and nom. Cross-section of cond-uctors mm2 | Min. No. of a signal wire in cond-uctor | Dia-meter of Cond-uctor mm | insu-lation thick-ness mm | Max. D.C. resis- tance of copper cond-uctor (20℃)Ω/km | Min. insulation resistance of rated work temperature Ω. km | Single Tensile force of cable N | Cable calculated Weight | XLPE Current Carrying (40℃)A | |||||||||
PVC insu- lated | XLPE insul- ated | ||||||||||||||||
Kg/km | |||||||||||||||||
Cu | Al | Cu | Al | PVC insu- lated | XLPE insu- lated | Cu | Al | Cu | Al | Cu | Al | Cu | Al | ||||
2×2.5 | 1 | — | 1.78 | 1.0 | 7.41 | — | 0.012 | 1.20 | 1914 | — | 74 | — | 64 | — | 32 | — | |
2×4 | 1 | 1 | 2.26 | 1.0 | 4.61 | 7.39 | 0.010 | 1.00 | 3009 | 1337 | 105 | 56 | 94 | 45 | 42 | 31 | |
2×6 | 1 | 1 | 2.76 | 1.0 | 3.08 | 4.91 | 0.007 | 0.70 | 4457 | 1927 | 146 | 72 | 133 | 59 | 49 | 40 | |
2×10* | 6 | 6 | 3.80 | 1.0 | 1.83 | 3.08 | 0.007 | 0.67 | 6942 | 3300 | 230 | 108 | 213 | 90 | 71 | 55 | |
2×16* | 6 | 6 | 4.80 | 1.2 | 1.15 | 1.91 | 0.007 | 0.65 | 10972 | 5024 | 363 | 165 | 337 | 139 | 97 | 75 | |
2×25* | 6 | 6 | 6.00 | 1.2 | 0.727 | 1.20 | 0.005 | 0.54 | 16930 | 7524 | 541 | 232 | 509 | 200 | 128 | 100 | |
2×35* | 6 | 6 | 7.00 | 1.4 | 0.524 | 0.868 | 0.005 | 0.54 | 23462 | 10354 | 751 | 319 | 709 | 276 | 158 | 122 | |
2×50* | 6 | 6 | 8.40 | 1.4 | 0.387 | 0.641 | 0.005 | 0.46 | 33004 | 14022 | 1035 | 416 | 987 | 368 | 194 | 148 | |
2×70* | 12 | 6 | 10.0 | 1.4 | 0.268 | 0.443 | 0.004 | 0.40 | 46922 | 20708 | 1416 | 551 | 1360 | 494 | 240 | 189 | |
2×95* | 115 | 12 | 11.6 | 1.6 | 0.193 | 0.320 | 0.004 | 0.39 | 63518 | 27454 | 1914 | 738 | 1840 | 664 | 296 | 230 | |
2×120* | 18 | 15 | 13.0 | 1.6 | 0.153 | 0.253 | 0.004 | 0.35 | 79822 | 34678 | 2378 | 892 | 2298 | 812 | 347 | 270 | |
*Compacted rotundity conductor |
BS four-core constant section of parallel clustered aerial insulated cable | |||||||||||||||||
Number and nom. Cross- section of cond- uctors mm2 | Min. No. of a single wire in conductor | Diam-eter of Cond-uctor mm | Insu-lation thick-ness mm | Max. D.C. resis-tance of copper cond-uctor (20℃) Ω/km | Min. insu- lation resis-tance of rated work tempe-rature Ω. km | Single Tensile force of cable N | Cable calculated Weight | XLPE Cur- rent Carr- ying (40℃)A | |||||||||
PVC insu- lated | XLPE insu- lated | ||||||||||||||||
Kg/km | |||||||||||||||||
Cu | Al | Cu | Al | PVC insu-lated | XLPE insu-lated | Cu | Al | Cu | Al | Cu | Al | Cu | Al | ||||
4×2.5 | 1 | — | 1.78 | 1.0 | 7.41 | — | 0.012 | 1.20 | 3828 | — | 149 | — | 129 | — | 29 | — | |
4×4 | 1 | 1 | 2.26 | 1.0 | 4.61 | 7.39 | 0.010 | 1.00 | 6050 | 2675 | 213 | 113 | 190 | 90 | 40 | 29 | |
4×6 | 1 | 1 | 2.76 | 1.0 | 3.08 | 4.91 | 0.007 | 0.70 | 8938 | 3853 | 293 | 146 | 267 | 119 | 45 | 37 | |
4×10* | 6 | 6 | 3.80 | 1.0 | 1.83 | 3.08 | 0.007 | 0.67 |