High voltage 300V electrical Aluminlum core PVC Insulated Flame Retardant Cables

Brand Name:New Baofeng
Minimum Order Quantity:500 Meter/MetersTrial Order
Delivery Time:Negotiable
Payment Terms:L/C,T/T
Place of Origin:Hebei, China (Mainland)
Price:Negotiable
Contact Now

Add to Cart

Active Member
Business type: Manufacturer Exporter
Address: Jinghe Hi-tech Industrial Zone, Hejian City, Hebei province,China
Supplier`s last login times: within 26 hours
Product Details Company Profile
Product Details
  • High voltage 300V electrical Aluminlum core PVC Insulated flame retardant cables
  • Product Standard


Enterprise standard. At the same time, apart from implementing IEC60332 or GB/T18380-2001 or the GB306-2007 the Public Safety industrial Standard for combustion retardant characteristics, products also adopt state standard (GB) for non-combustion-resisting type equivalent to the products.

  • Usage


This product is suitable for use in all places using non-com-bastion-retardant type power cable, electrical equipment-use wire and cable and all corresponding products and at the same time requires combustion-retardant environment and conditions.

  • Property for Use


1.Rated voltage(U0/U), from 300/300V to 26/35KV according to different kinds of product series.

2.The max. word temperature of cable for a long period are:70℃, 90℃ and 105℃.

3.For short circuit(5s), the max. work temperature of conductor does not exceed 160℃ for 70℃;250℃ for 90℃.

4.The temperature for laying cable is not less than 0℃.

5.Cable bend radius implements corresponding non-com-bastion-retardant cable standard stipulation.

6.Combustion-retardant characteristics can be divided into categories A and C(category B is not recommended).

a.ZC-type combustion-retardant cable is used in general combustion-retardant places requiring IEC60332-3C category.
b.ZA-type combustion-retardant cable is used in combustion-retardant places requiring relatively harsh IEC60332-3A category.
c.Single cable should reach the requirement of IEC60332-1(2)non-burning, that is, self-extinguishing nature. Multi-cable or a bundle of cable will only burn in a certain scope after reaching the IEC60332-3 standard and will extinguish itself.

  • Scope of Application


Nuclear power station, underground railway, telecommunications station, high rises, petroleum, metallurgy, power plant installations, tunnel, etc.

China High voltage 300V electrical Aluminlum core PVC Insulated Flame Retardant Cables supplier