Converter Used Main Circuit Power Cable
■ Product Standard
Enterprise standard
■ Application
It is suitable for power transmission between converter and motor.
■ Type and Designation
Type | Designation |
BPYJVP | XLPE insulated PVC sheathed woven copper wire shield converter used main circuit cable |
BPYJVP1 | XLPE insulated PVC sheathed copper wire wind shield converter used main circuit cable |
BPYJVP1-2 | XLPE insulated PVC sheathed copper wire wind copper tape wrapped double shield converter used main circuit cable |
BPYJVP3 | XLPE insulated PVC sheathed Al/plastic compound tape shield converter used main circuit cable |
ZR-BPYJVP | XLPE insulated PVC sheathed woven copper wire shield flame-retardant converter used main circuit cable |
ZR-BPYJVP1 | XLPE insulated PVC sheathed copper wire wind shield flame-retardant converter used main circuit cable |
ZR-BPYJVP1-2 | XLPE insulated PVC sheathed copper wire wind copper tape wrapped double shield flame-retardant converter used main circuit cable |
ZR-BPYJVP3 | XLPE insulated PVC sheathed Al/plastic compound tape shield flame-retardant converter used main circuit cable |
WDZ-BPYJYP | XLPE insulated PO sheathed woven copper wire shield low-smoke halogen-free flame-retardant converter used main circuit cable |
WDZ-BPYJYP2 | XLPE insulated PO sheathed copper tape shield low-smoke halogen-free flame-retardant converter used main circuit cable |
WDZ-BPYJYP1 | XLPE insulated PO sheathed copper wire wind shield low-smoke halogen-free flame-retardant converter used main circuit cable |
WDZ-BPYJYP1-2 | XLPE insulated PO sheathed copper wire wind copper tape wrapped double shield low-smoke halogen-free flame-retardant converter used main circuit cable |
WDZ-BPYJYP3 | XLPE insulated PO sheathed Al/plastic compound tape shield low-smoke halogen-free flame-retardant converter used main circuit cable |
Type | Code | Explanation |
Series code | BP | Converter cable |
Insulation code | YJ | XLPE insulated |
Sheath code | V Y | PVC sheath Low-smoke halogen-free PO |
Structural characters | P P2 P1 P3 | Woven copper wire or tinned copper wire Copper tape wrapped Copper wire wind Al/plastic compound tape wrapped |
Flame-retardant code | omitted ZR WDZ | Non flame-retardant Flame-retardant Low-smoke halogen-free flame-retardant |
■ Indication example
0.6/1kv copper core XLPE insulated, woven copper wire shield, PVC sheathed flame-retardant converter used main circuit cable, 3×185+3×35mm2 is described as: ZR-BPYJVP-0.6/1 3×185+3×35
■ Using feature & Main Technical Performance
1. Rated Voltage U0/U:0.6/1KV.
2. The Max. Temperature allowed of conductor for long-term working is 90℃.
3. In short-circuit (Max. Long term is continue on more than 5 seconds),the highest temperature of conductor is no more than 250℃.
4. Environment temperature in laying the cable should be no smaller than 15 times of cable outer diameter.
5. It has a stronger electrical shock resistance, it can stand the impulse voltage under high speed and frequent converting.
6. It has a good shield performance. It can lower the negative effect by the high harmonious wave in the output frequency converter.
7. D.C. Conductor resistance complies with the stipulations of GB/T3956.
8. Working frequency voltage test for cable with 3.5kv/5min without puncture.
9. Flame retardant cable could endure firing test is bundle stipulated in GB/T18380.3.
10. Low-smoke halogen-free flame retardant cable could endure firing test in bundle as GB18380.3.Smoke density in firing should comply with stipulations of GB/T17651-1998(IEC1034).PH value of solution water of gas separated out should be less than 4.3, and electric conductivity rate should be no more than 10μs/mm and comply with stipulations of IEC754-2.