Product Details

ISO Current Transformer Test Set With Customized Continuous Running Primary Current


Product Name:

Primary Current Injection Test Set SLQ


Equipment Description:

​SLQ primary injection test set is a high current generator instrument. It is applied in current transformer test , circuit breaker test and so on. Adjustable output current, smooth in current rise, large scope of load variation, easy and safe operation.


Features:

1. Large current generator as the current source for the test of electrical equipment for thermal stability, dynamic stability test when low-voltage high current power supply, such as air circuit breaker, contactor, relay temperature rise test and tripping.

2. Single phase high current generator to test the three phase should be carried out separately.

3. Three phase high current generator is mainly used for three-phase electrical products testing, and also can be used to test single-phase electrical products. The control scheme of three phase and single phase high current generator is the same, but the three-phase current generator output of three-phase current.

4. The high current generator is composed of three parts: the transformer, the voltage regulator and the control.


Technical Parameters:

Type

Capacity

(kva)

Power supply

Output

Impedance voltage %

Idle current %

mode

I

(A)

V

(V)

I

(A)

V

(V)

SLQ-5/500

3

13.6

220

500

5

>8

>6

single

SLQ -5/1000

5

22.7

220

1000

5

>8

>6

single

SLQ -10/2000

10

46

220

2000

5

>8

>6

Separated

SLQ -12/4000

12

30

400

2000/4000

6/3

>8

>6

Separated

SLQ -15/5000

15

37.5

400

2500/5000

6/3

>8

>6

Separated

SLQ -150/25kA

150

375

400

25000

6

>8

>6

Separated