Home /Custom Fabrication Services /

FRC Series High Voltage Test Equipment HV Divider Impedance 200MΩ - 1200MΩ

FRC Series High Voltage Test Equipment HV Divider Impedance 200MΩ - 1200MΩ

Brand Name:GDZX
Certification:ISO9001
Model Number:FRC
Minimum Order Quantity:1
Payment Terms:L/C, T/T, Western Union, MoneyGram
Place of Origin:CHINA
Contact Now

Add to Cart

Verified Supplier
Location: Wuhan Hubei China
Address: No.1 Fenghuangyuan Second Road, Jiangxia District, Wuhan City, Hubei Province, China
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

100kV 150kV 200kV FRC series High Voltage Test Equipment HV Divider

High Voltage Capacitive Voltage Divider

Product Description

ZX-FRC-1.0 digital kilovoltmeter consists of a high stabilized resistive-capacitive type passive high-voltage divider and a precision digital voltmeter for measuring AC/DC high voltage on the site of electric power systems and in various high-voltage laboratories. Both of them with measuring cable, power supply cord, and operating manual are placed in a portable aluminium case for easy carrying and use.

Preparation Before Test (Measurement)

(1)High voltage divider is arranged in a proper position. Be sure that, an adequate clearance should be kept to surrounding objects. The minimum clearance should not be less than the height of the volgate divider.

(2)Grounding connection: The ground terminals of voltage divider basement and of digital voltmeter should be reliably connected to ground by braided copper wire.

(3)Measuring signal connection: The supplied coaxial measuring cable is specially prepared for connecting from voltage signal output socket of divider bacement to the signal input socket of digital voltmeter. If should not be replaced by other coaxial cable or any connecting wire, because of capacitive match to the voltage divider.

(4)High voltage connection: The high voltage terminal to be measured is connected to the top connecting screw MIO of voltage divider by HV leads. Be sure that, an adequate angle of 75°~90°between HV leads (inclined downward) and vertical axis of voltage divider should be kept during calibration and use for precise measurement.


Range Selector

Press the range selector to change the measuring range. In case of measured voltage less than 20kV, turn the range selector in lower range for higher measuring accuracy. When the measured voltage is higher than 20kV, turn the voltage selector in higher range.


Packing List


No.ItemQty
1High voltage divider1
2Digital kilovoltmeter1
3Coaxial measuring cable1
4Power line1

Technical parameters

Ratio1000:1
Insulating mediumdry type dielectric material
AC measuring methodreal effective value measurement
Condition of circumstanceTemperature0~40℃
Humidity≤85%RH

Main Specifications

ModelVoltage classAccuracyVoltmeter rangeimpedance()Signal line lengthDimension (mm3)Weight (kg)
SGB-50CAC:50kV,DC:50kVAC:1.0% DC:0.5%Low:0-20kV,High:0-50kV6003m180*180*6206
SGB-100CAC:100kV,DC:100kVAC:1.0% DC:0.5%Low:0-20kV,High:0-100kV12003m180*180*9008
SGB-150CAC:150kV,DC:150kVAC:1.0% DC:0.5%Low:0-20kV,High:0-150kV18004m250*250*110015
SGB-200CAC:200kV,DC:200kVAC:1.0% DC:0.5%Low:0-20kV,High:0-200kV24004m250*250*133017
SGB-300CAC:300kV,DC:300kVAC:1.5% DC:1.0%Low:0-20kV,High:0-300kV36005m250*250*1900

22

China FRC Series High Voltage Test Equipment HV Divider Impedance 200MΩ - 1200MΩ supplier

FRC Series High Voltage Test Equipment HV Divider Impedance 200MΩ - 1200MΩ