Central Air Source Heat Pump Characters
1, efficient
◆ The unit adopts a special pump for heat pump type, which matches
the high-efficiency condenser with the evaporator and the inlet
expansion valve. The four components are perfectly matched.
2, reliable operation
◆ The unit has 7 kinds of safety protection measures to ensure the
normal operation of the unit.
◆ The unit is designed for double circuit and double compressor.
When a single compressor fails, the other compressor can still
operate normally without affecting the customer's use.
◆ All units are tested by the national safety inspection system
before leaving the factory to ensure that the unit performance
meets national standards.
3, intelligent management
◆ The unit adopts the microcomputer touch control system to provide
the simplest and most thoughtful operation interface and timely
feedback of various maintenance information.
◆ The unit control system can be connected to the user's central
control system, and the customer can understand the unit's
operation at all times.
4. Comfortable. The water system has high stability and can
maintain a constant indoor temperature. In addition, the heating
and cooling methods are closer to the human body's temperature,
which makes the refrigeration and heating more comfortable and does
not give the user a feeling of chilling and hot.
Heating model code name.pdf
Model | SLNA-032Y | SLNB-035Y | SLNB-047Y | SLNC-075Y | |||
Compressor capacity | 10HP | 12.5HP | 15HP | 25HP | |||
Function | Heating and Cooling | Heating and Cooling | Heating and Cooling | Heating and Cooling | |||
Electricity | 380V-3N-50Hz | 380V-3N-50Hz | 380V-3N-50Hz | 380V-3N-50Hz | |||
Working conditions | ℃ | -25~+45 | -25~+45 | -25~+45 | -25~+45 | ||
Data | Heata | Nominal capacity | KW | 21.5 | 22.3 | 28.1 | 44.5 |
Input power | KW | 9.1 | 9.4 | 11.7 | 18.3 | ||
COP | / | 2.3 | 2.35 | 2.4 | 2.4 | ||
Heating IPLV(H) | 2.7 | 2.7 | 2.7 | 2.7 | |||
Coolb | Nominal capacity | KW | 25 | 28 | 39 | 62 | |
Input power | KW | 10 | 10.4 | 13.1 | 20.7 | ||
COP | / | 2.5 | 2.7 | 2.9 | 3 | ||
Cooling IPLV(C) | 2.7 | 2.7 | 2.7 | 2.7 | |||
A7W35c | KW/COP | 32.0/4.1 | 35.0/4.1 | 47.0/4.1 | 75.0/4.2 | ||
A2W35 | KW/COP | 27/3.60 | 28.5/3.60 | 39.5/3.20 | 62.5/3.20 | ||
A-7W35 | KW/COP | 21.5/2.8 | 23.5/2.9 | 32/2.9 | 50/2.9 | ||
A-15W55 | KW/COP | 19.7 /1.94 | 20.2 /1.94 | 28.1/1.94 | 45.5 /1.97 | ||
A-20W45 | KW/COP | 18.1/2.02 | 18.7/2.02 | 23.6/2.03 | 37.4/2.04 | ||
Max. running currency | A | 25 | 27 | 35 | 56 | ||
Compressor quantity | set | 2 | 1 | 2 | 2 | ||
Refrigerant/charging quantity kg | / | R22/3.7*2 | R22/9 | R22/10 | R22/15*2 | ||
Air blow type | / | Top | Side | Top | Top | ||
Water pipe diameter | mm | 32 | 32 | 50 | 50 | ||
Rating flow | m³/h | 5.5 | 5.9 | 8.3 | 12.6 | ||
Water side pressure loss | kPa | ≤45 | ≤45 | ≤45 | ≤45 | ||
Noise level | dB(A) | 62 | 62 | 62 | 62 | ||
Overall dimensions(L×W×H) | mm | 1530×750×1370 | 1490×900×1900 | 1450×1100×2080 | 2100×1100×2080 | ||
Weight | kg | 320 | 350 | 470 | 730 |
Yushen Central Air Source Heat Pump
Central Air Source Heat Pump Applications
It is suitable for the cooling &heating of office building, villa, hotel and community. In summer, it provide water of 7℃ for cooling; in winter it provide water of 50℃