Home /Heat Pump Water Heaters /

Low Noise Indoor Air Source Heat Pump / Heat Pump Air Conditioning Unit

Low Noise Indoor Air Source Heat Pump / Heat Pump Air Conditioning Unit

Brand Name:Yushen
Certification:CCC, ISO, Energy Concervation Product
Model Number:Indoor Air Source Heat Pump
Minimum Order Quantity:1 set
Delivery Time:1-2 weeks
Payment Terms:T/T
Contact Now

Add to Cart

Active Member
Location: Shanghai Shanghai China
Address: Foreign sales office: 588 South Qilianshan Road ,Putuo area, Shanghai,China
Supplier`s last login times: within 27 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Low Noise Indoor Air Source Heat Pump / Heat Pump Air Conditioning Unit


Indoor Air Source Heat Pump Features
1. Large-scale flat fins: extend the defrosting time interval, make the heat more durable; defrosting and draining quickly.
2, large static pressure box: the fins are more uniform over the wind, and the heat exchange efficiency is high.
3, jet increase: the lowest ring temperature -25 ° C, the highest water output 65 ° C.
4, compact design: the floor space is reduced by nearly 40%.
5, original noise reduction technology, the unit's overall noise is only 65dB (A), very suitable for central heating
Recommended area: Energy-saving building heating in the Beijing-Tianjin-Hebei region 2000 to 2400 m2, cooling 1400 to 1700 m2

Indoor Air Source Heat Pump Applications

  • It is suitable for the cental heating of office building, hotel and residential community.
  • In winter it provide water of 50℃ for heating to the ender to produce heat.

Indoor Air Source Heat Pump Advantages

  • It could work in extreme environment /Suitable for environmental temperature:-25℃ to +45 ℃ /-13℉ to 113 ℉
  • Yushen air source heat pump is 35% more powerful than other products, long heating time and less defrosting time
  • No capacity decay under low temperature, keep high COP in winter
  • Quality Components such as Copeland compressor, Danfoss valves
  • Pay attention to details such as every stainless-steel screw has cushion to prevent from water corrosion
  • Clean and clear wiring and lining
  • 100% finished products testing
  • Having only one unit which could both heat and cool to maintain means lower repair costs and less work in general.

Indoor Air Source Heat Pump Parameter


code name.pdf

ModelSDNA-075YSDNA-090YB
Compressor capacity25HP30HP
FunctionHeatHeat
Electricity380V 3N-50Hz380V 3N-50Hz
Working conditions-25~+45-25~+45
DataHeataNominal capacityKW44.556.2
Input powerKW18.323.4
COP/2.42.4
Heating IPLV(H)2.72.7
A7W35cKW/COP75.0/4.290.0/4.2
A2W35KW/COP62.5/3.2079.0/3.20
A-7W35KW/COP52.5/3.063.2/3.0
A-15W55KW/COP45.5 /1.9756.2/1.97
A-20W45KW/COP37.4/2.0447.2/2.04
Max. running currencyA5670
Compressor quantityset24
Refrigerant/charging quantity kg/R22/10*2R22/5*4
Air blow type/TopTop
Water pipe diametermm5050
Rating flowm³/h12.612.6
Water side pressure losskPa≤45≤45
Noise leveldB(A)6262
Overall dimensions(L×W×H)mm2100×1100×20802100×1100×2080
Weightkg730830

Packing