Outdoor SF6 High Voltage Circuit Breaker AC 50Hz LW8-40.5


1.General


1.1 LW8-40.5 Outdoor HV SF6 circuit breaker is an outdoor HV electrical equipment of three-phase, AC, 50Hz and it's suitable for control and protection of power transmission and distribution system, it also can be used to tie circuit breaker and break/make capacitor bank, and also can attach circuit breaker in it for measurement and protection.

1.2 LW8-40.5 Outdoor HV SF6 circuit breaker adopts CT14 spring operation mechanism.

1.3 The circuit breaker meets the requirements of national standard : GB1984-89 AC High-Voltage Circuit breakers, and IEC56 AC High-Voltage Circuit breakers.

1.4 Main features of the Circuit breaker


a. Good breaking performance, short-time arcing time,
long electrical duration and with the ability of continuous breaking of 16 times under the rated voltage without change of SF6.
b. Reliable insulation, to be up to 40.5Kv/10min at gas pressure of zero point of meter.
c. High mechanical reliability, High making ability, frequent operation is available.
d. Without return while closing and opening capacitor bank of 400A.
e. Cut off long line of 25.50km and has no re-burn.
f. Simple structure, small size, long free time is no need to overhaul.

1.5. Application environment

a. Altitude to be not more than 1000m
b. Ambient temperature: -30ºC - + 40ºC, the average value of 24H to be not more than 35ºC;
c. Relative humidity: the daily average value to be not more than 95%, monthly average value to be not more than 90%,
d. Speed of wind: not more than 35km/s
e. Contamination condition to be III grade, porcelain bushing creepage distance shall be 1050 mm (nominal creepage ratio to be not less than 25mm/kV);
f. The ambient air should be free of the flammable material, explosive danger, chemical corrosive and intensive shake.

2. Main technical parameters

2.1 LW8-40.5 Circuit breaker main technical parameters to see table 1.
2.2 Assembly and adjustment parameters of circuit breaker to see table 2.

Table 1

No.ItemUnitParameter
1Rated voltagekV40.5
2Rated insulation level1min power frequency withstand voltagekV185/215(fracture)
Lightning impulse withstand voltage95/118(fracture)
3Rated currentA2000
4Mechanical endurancetime5000
5Rated pressure of SF6 gas(20ºC meter pressure)Mpa0.45
6Locking pressure (20ºC meter pressure)Mpa0.40
7Lowest ambient temperatureºC-30
8Rated short-circuit breaking currentkA31.5
9Rated short-circuit making current(peak)kA80
10Rated short time withstand current(thermal current)kA31.5
11Rated peak withstand current(dynamic current)kA80
12Rated out-of-phase breaking currentkA7.9
13Breaking times of the rated short-circuit breaking current:time16
14Close times≤0.1
15Open times≤0.06
16Rated operation sequence
O-0.3s-CO-180s-CO
17Rated breaking/opening current of single capacitor groupA400
18Last time of short circuit currents4
19SF6 leakage rate (yearly)
≤1
20Moisture Content of SF6 gas(20ºC)Ppm(v/v)≤150
21Rated operating voltage of spring operation mechanism

Voltage of closing and opening coilVAC 220, 380
DC:48, 110 , 220
Voltage of energy storage motorVAC 220
DC 220
22Weight of SF6 gaskg8
23Weight of circuit breaker (including operation mechanism)kg1400


Table 2

No.ItemUnitTechnical RequirementsTest conditions and methods
1Travel of movable contactmm95±2Measurement of movable contact travel refer to darawing12
2Clearance between contactsmm605±1.5Measurement of Clearance between movable and fixed contact refer to drawing 12a
3Three-phase switch-on asynchronyms≤3Measurement of pole distance difference between movable and fixed contact refer to darawing14
4Three-phase switch-off asynchronyms≤2Measurement of pole distance difference between movable and fixed contact refer to drawing 15
5Resistance of main loopμΩ≤120Measurement to DC voltage drop method, put in 100A
6Speed at instant of contacts touchingm/s3.2±0.2Rated voltage and measurement method refer to drawing 14
7Speed at instant of contacts disconnectingm/s3.4±0.2Rated voltage and measurement method refer to the drawing 15
8Cuisine stroke of makingmm10+0.5 -0.1Refer to drawing 6 under the closing status
9positioning gap of Cuisine stroke of makingmm1-2Refer to drawing 6 under the closing status
10Partial charging
40.5kV
25.7kV
PC20At rated gas pressure, use partial instrument to put 40.5kV between two outgoing wires for 1min, then drop to 25.7kV equably
PC10