Home /Energy & Mineral Equipment /

65.5kW COP 3.38 High Efficiency Air Cooled Modular Chiller / Heat Pump Units

65.5kW COP 3.38 High Efficiency Air Cooled Modular Chiller / Heat Pump Units

Brand Name:EuroKlimat
Certification:ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Model Number:EKAC 230B(R)
Minimum Order Quantity:1
Delivery Time:20 working days after received your payment
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Active Member
Location: Dongguan Guangdong China
Address: Euroklimat Industrial Park, Huangjiang Dongguan Guangdong China 523766
Supplier`s last login times: within 2 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Low-temp high-efficiency model Air-cooled Heat Hump Unit


Specifications:


EKAC modular air-cooled heat pump units combines more than 40 years of Italian air-cooled heat pump design experience and the application practices of modular units in China, so as to meet customers' requirements on product efficiency, safety, smartness and comfort. This series of units have diversified models and are applicable to various environments, such as villas, hotels, recreation centers, hospitals, dining halls, office buildings, supermarkets, and various industrial processes that requires cooling.


Technical data sheet


Model EKAC 230BEKAC 230BREKAC 460BEKAC 460BREKAC 690BEKAC 690BR
Unit combinationMaster unitEKAC 230BMEKAC 230BRMEKAC 230BMEKAC 230BRMEKAC 230BMEKAC 230BRM
slave unit---EKAC 230BSEKAC 230BRS2EKAC 230BS2EKAC 230BRS
Nominal cooling capacitykW65.565.5131131196.5196.5
USRT18.6318.6337.2637.2655.8855.88
×104kcal/h5.635.6311.2611.2616.9016.90
Nominal heating capacitykW--69--138--207
USRT--19.62--39.2--58.9
×104kcal/h--5.93--11.9--17.8
Total power of nominal cooling capacitykW19.419.438.838.858.258.2
Total power of nominal heating capacitykW--19.2--38.4--57.6
Power supply 380V/3N~/50Hz
RefrigerantType R22
Control Electronic expansion valve
CompressorType Fully hermetic volute compressor
Lubricant Mineral oil (SUNISO 3GS)
Qty.Set224466
FanType High-efficiency vacuum braze-welded panel type
Qty.Set224466
Water side heat exchangerType High-efficiency vacuum braze-welded panel type
Water flow for
cooling
3
m /h
11.311.322.622.633.933.9
Water flow rate
in heating mode
3
m /h
--11.9--23.8--35.7
Water resistancekPa454545454545
Recommended diameter for general inlet/outlet water pipeinch≥2≥2≥3≥3≥3≥3
Power cable specificationSection area of live line2
mm
≥10≥10≥35≥35≥70≥70
Qty. of live lines 3
Section area of null line2
mm
≥4
Qty. of null lines 1
Section area of grounding line2
mm
≥10≥10≥16≥16≥35≥35
Qty. of grounding lines 1
DimensionsL x Hmm2012×1840
Widthmm8808802125212533703370
Unit weightNet weightkg5005201000104015001560
Operating weightkg5105301020106015301590

Model EKAC 920BEKAC 920BREKAC 1150BEKAC 1150BREKAC 1380BEKAC 1380BR
Unit combinationMaster unitEKAC 230BMEKAC 230BRMEKAC 230BMEKAC 230BRMEKAC 230BMEKAC 230BRM
slave unit3EKAC 230BS3EKAC 230BRS4EKAC 230BS4EKAC 230BRS5EKAC 230BS5EKAC 230BRS
Nominal cooling capacitykW262262327.5327.5393393
USRT74.5174.5193.1493.14111.77111.77
×104kcal/h22.5322.5328.1628.1633.7933.79
Nominal heating capacitykW--276--345--414
USRT--78.5--98.1--117.7
×104kcal/h--23.7--29.7--35.6
Total power of nominal cooling capacitykW77.677.697.097.0116.4116.4
Total power of nominal heating capacitykW--76.8--96.0--115.2
Power supply 380V/3N~/50Hz
RefrigerantType R22
Control Electronic expansion valve
CompressorType Fully hermetic volute compressor
Lubricant Mineral oil (SUNISO 3GS)
Qty.Set8810101212
FanType High-efficiency vacuum braze-welded panel type
Qty.Set8810101212
Water side heat exchangerType High-efficiency vacuum braze-welded panel type
Water flow for
cooling
3
m /h
45.245.256.556.567.867.8
Water flow rate
in heating mode
3
m /h
--47.6--59.5--71.4
Water resistancekPa454545454545
Recommended diameter for general inlet/outlet water pipeinch≥4≥4≥4≥4≥5≥5
Power cable specificationSection area of live line2
mm
≥95≥95≥120≥120≥150≥150
Qty. of live lines 3
Section area of null line2
mm
≥4
Qty. of null lines 1
Section area of grounding line2
mm
≥50≥50≥60≥60≥75≥75
Qty. of grounding lines 1
DimensionsL x Hmm2012×1840
Widthmm461546155860586071057105
Unit weightNet weightkg200020802500260030003120
Operating weightkg204021202550265030603180

Note:
■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.
■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature
7°C/6°C.
■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK
does not provide the pipes.
■ Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists
the parameters for common module combinations.
■ For on-site electric wiring, see the name plate or installation menu of the unit.


Description:


1. Based on its leading-edge design for air cooled and heat pump units in Europe as well as the wide use of its air-cooled units in China, EK has launched this series of innovative modular air-cooled water chiller (heat pump) units. The full-load COP of this series is higher than that the energy saving product certification standard

2. Each modular unit has two power gears. When multiple modular units are combined, there could be many power gears. Fully-optimized model selection and matching practice ensures that the units can always save as much energy as possible. When operating with a partial load (99% of full operation time), the EER is even 4% higher.

3. With an optional 2-way valve water control feature, the unit can send out signals to turn off corresponding chilled water valves. This enables automatic flow control for pumps in line with the transducer, which helps save more energy.

4. The unit features modular design and starts up in steps to ease the shock on the power grid caused by startup current.

5. The unit has undergone strict and long-duration tests according to the most stringent standards, and can work reliably to providing cooling when the ambient temperature is as high as 48℃ and heating when the ambient temperature is as low as -10℃.

6. The system features built-in high/low pressure protection, cooling freezing protection, winter freezing protection, compressor overload protection and water pressure-drop switch etc. to maximize the safety of the unit.

7. The unit uses a 500-step PMV electronic expansion valve for precise PID control, dynamic and real-time adjustment of the cooling system, and higher-precision water temperature control. This helps optimize the performance of each and every part of the system. The unit can work reliably under any load and automatically adapt to changing ambient temperatures, completely eliminating cooling system vibration.

8. The entire unit features vibration isolation design and multiple noise reduction processes. Both noise level and vibration level of the unit take the lead in the industry thanks to its name-brand quite hermetic volute Compressors and two-gear quiet fans. The noise level of the unit is significantly reduced using professional noise reduction practices, such as comparing, choosing and improving fans, motors, structures and pipelines based on noise spectrum analysis results.

9. Innovative smart silencing mode can automatically adjust the fan rev (high/low) according to outdoor temperature and the operation status of the unit. This makes the unit even quieter in operation mode.

10. The unit needs no additional equipment room, and can be mounted on the floor, building roof, etc. Modular design makes each unit small in dimension and suitable for transportation by cargo elevator, thus saving hoist cost during construction. The unit can also be installed step by step to shorten the construction period.

11. Each unit has a separate refrigerant circuit. This reduces the probability of refrigerant leakage which could damage the ozonosphere.

12. The unit uses a micro-computer controller with a large LCD screen to facilitate operation. Each controller can control and dynamically monitor the operation of up to 16 units. This facilitates centralized management.


China 65.5kW COP 3.38 High Efficiency Air Cooled Modular Chiller / Heat Pump Units supplier

65.5kW COP 3.38 High Efficiency Air Cooled Modular Chiller / Heat Pump Units

Inquiry Cart 0