Home /Container /

1500KW Container Load Bank for AC Genset Testing

1500KW Container Load Bank for AC Genset Testing

Brand Name:Triumph Load
Certification:ISO9001:2008
Model Number:AC400-1500KW
Minimum Order Quantity:1 set
Delivery Time:within 35 days
Payment Terms:T/T,L/C,Western Union
Contact Now

Add to Cart

Active Member
Location: Shijiazhuang Hebei
Business type: Manufacturer, Exporter
Address: No68 Jianshe Street,Shijiazhuang,Hebei,China
Supplier`s last login times: within 47 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

1500KW Container Load Bank for AC Genset Testing


Compact and Lightweight design that is ideal for moving from job site to job site or within your facility.


Introduction:

It offers the most robust, high-capacity designs in the industry. It is setting the standard with intelligent operator controls, safety indication layouts, adjustable load step resolution, and lightweight designs. It is the perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems.


Main features


1. Multiple control mode: (1) manual panel control (2) remote control (3)software control

2. Multiple display function: voltage, current, frequency, power factor, active power, reactive power, apparent power etc.

3. Multiple protection function: overvoltage, overcurrent, overheat, over low blowing rate, blower overheat, blower phase sequence reverse protection, smoke alarm etc.

4. Forced air cooling: industrial heavy duty fan, horizon air intake, upwards outlet, low noise.

5. Power consumption components: made by special alloy resistance, high temperature resisting, high heat dissipation capability, high heat stability, no naked light, safety and reliability. Running temperature is 1/3 of rating.

6. Weather-proof structure: containerized structure provides ultra protection, protection grade higher than IP55.

7. Material and coating: the body adopt cold-rolled steel plate that processed by galvanizing corrosion protection, powder coated and spray paint.

8. Integrated & modularization design: compact structure, easy to installation, maintenance and transportation.

9. Software control: it can test and display voltage, current, frequency, power factor, active power, reactive power, apparent power etc, the test result can be store & print and form all kinds of curve, chart and test report.


Technical Paramters of 1500KW Container Load Bank for AC Genset Testing


Rated Load Voltage

400V, 3 phase 4 wire, 50HZ

Rated Load Power

1500KW

Power Factor

1

Min Load Step

1KW

Resistive Load Steps

1kw,2kw,2kw,5kw,10kw,10kw, 20kw,50kw,100kw,200kw,200kw, 200kw,200kw, 500kw total 14 steps

Duty Cycle

Continuous

Cooling

Forced air cooling by industrial fan, low noise

Ventilation Method

Horizontal inlet air and upwards exhaust cooling

Enclosure

Container type with a ladder, air inlet and outlet with mesh enclosure and protection door

Max Protection Grade

IP55

Ambient Temperature

-10℃~+50℃

Dimensions

6058 mm*2438mm*2591mm(length*wide*high)

Weight

About 1700kgs

Type for Choice

Manual Type

Control Mode

Panel

Display Instrument

voltmeter, amperemeter display single phase voltage and current

Automatic Type

Control Mode

Panel or software


The application of load bank


A load bank is an electrical apparatus used to verify the performance of an electrical power source. The most common application for the equipment is to provide an exercise "load" for standby emergency generators. These emergency generators are typically installed at hospitals, hotels, office buildings, skyscrapers, water treatment facilities, data centers, large retail facilities, and other such sites. The load banks provide a precise and stable electrical load for the generators. The electrical load created by load banks allow verification of the performance of the generator on a scheduled maintenance interval. Many other applications for load banks exist other than standby generator testing. The generator manufacturers require load banks for research and design programs as well as production testing. The military utilizes load banks in various applications such as testing of power supplies and generators for aircraft, frequency convertors, submarines, and missile defense systems. Computer and network Uninterruptible Power Supplies (UPS) also require load bank testing of both the inverter and battery inputs.

China 1500KW Container Load Bank for AC Genset Testing supplier

1500KW Container Load Bank for AC Genset Testing

Inquiry Cart 0