High Accurate Megger Digital Insulation Tester Max 5T Ohm , Auto Calculate PI and DARt YH510
Quick Detail:
☉Test Voltage from 250V~5000V
☉Insulation Resistance up to 5TΩ
☉ Short Current up to 3mA
☉ Auto Calculate PI(Polarization Index) and DAR(Dielectric absorption ratio)
☉ Step-Voltage Measurement
☉ Temperature measurement
☉ Temperature compensation for insulation Test
Features
High Voltage Digital Insulation Tester YH510
☉ Checking the insulation of high-voltage electrical equipment
(electric motor, transformer, and cable, etc)
☉Test Voltage from 250V~5000V
☉Insulation Resistance up to 5TΩ
☉ Short Current up to 3mA
☉ Auto Calculate PI(Polarization Index) and DAR(Dielectric absorption ratio)
☉ Step-Voltage Measurement
☉ Temperature measurement
☉ Temperature compensation for insulation Test
☉ Leakage Current measurement
☉ Data Storage function and uploading to PC by USB2.0 interface
☉ Power Supply:LR6 Battery×6/ rechargeable battery Ni~MH 7.2V
(Charger;Input Voltage 100V~240V ; Frequency 50Hz~60Hz, Output Voltage 12V DC 3A)
☉ Timer Function
☉Weight 2.5kg (not including Battery)
☉Size 284mm(L)×230mm(w)×125mm(H)
Test Voltage
☉ Test Voltage Range; DC250V~ DC 5.00kv
☉ Voltage Set:
☉ Wide adjust;(250V; 500V; 1000V; 2.5kv; 5kv)
☉ Fine adjust (250V~1KV; Step 25V; 1KV~5KV, Step 100V)
☉ Accuracy; 5%
☉ Step mode:500V, 1.0KV, 1.5KV, 2.0KV, 2.5KV
☉ Test Current 1nA~3mA
Temperature compensation
For obtaining the insulation resistance under a temperature other than current ambient temperature.
Converts the measured value of resistance to the insulation resistance under a reference temperature, and displays the result.
Depending on the different properties of test objects, there are 10 modes of compensation.
Insulation Resistance
Set test voltage | Test range | Threshold value of basic error |
250 V DC | 0.01 MΩ ~ 2.5 GΩ | ±(5% rdg + 5 dgt) |
2.51 GΩ ~ 250 GΩ | ±(20% rdg +10 dgt) | |
500 V DC | 0.01 MΩ ~ 5.0 GΩ | ±(5% rdg +5 dgt) |
5.01 GΩ ~ 500 GΩ | ±(20% rdg +10 dgt) | |
1000 V DC | 0.01 MΩ ~ 10 GΩ | ±(5% rdg +5 dgt) |
10.1 GΩ ~ 500 GΩ | ±(20% rdg +10 dgt) | |
501 GΩ ~ 999 GΩ | ±(30% rdg +20 dgt) | |
2.5 kV DC | 0.01 MΩ ~ 25 GΩ | ±(5% rdg +5 dgt) |
25.1 GΩ ~ 500 GΩ | ±(20% rdg +10 dgt) | |
501 GΩ ~ 999 GΩ | ±(30% rdg +20 dgt) | |
1 TΩ ~ 2.5 TΩ | ±(30% rdg + 40 dgt) | |
5 kV DC | 0.01 MΩ ~ 50 GΩ | ± (5% rdg + 5 dgt) |
50.1 GΩ ~ 500 GΩ | ±(20% rdg + 10 dgt) | |
501 GΩ ~ 999 GΩ | ±(30% rdg + 20 dgt) | |
1 TΩ ~ 5 TΩ | ±(30% rdg + 40 dgt) |
Leak Current
Range | Measuring range | Threshold value of basic error |
10 nA | 1.00 nA ~ 9.99 nA | ± (15% rdg. + 1 nA) |
100 nA | 9.0 nA ~ 99.9 nA | ± (15% rdg. + 5 dgt) |
1000 nA | 100 nA ~ 999 nA | ± (2.5% rdg. + 5 dgt) |
10 μA | 0.90 μA ~ 9.99 μA | |
100 μA | 9.0 μA ~ 99.9 μA | |
1000μA | 90 μA ~ 999 μA | |
3 mA | 0.90 mA ~ 3.00 mA |
Voltage Test
Test mode | DC voltage | AC voltage |
Test range | ± (50 V ~ 1000 V) | 50 V ~ 750 V/(50 Hz ~ 60 Hz) |
Precision error | ± (5% rdg + 5 dgt) | |
Input resistance | About 10 MΩ |
Temperature Test
Measuring range | Measuring precision |
-10 °C ~ 0.1 °C | ± 1.5 °C |
0.0 °C ~ 40.0 °C | ± 1.0 °C |
40.1 °C ~ 70.0 °C | ± 1.5 °C |
WARRATY: one year