Home /Heat Pump Water Heaters /

Silent Central Heating And Cooling System / High Speed Heat Pump Central Heating

Silent Central Heating And Cooling System / High Speed Heat Pump Central Heating

Brand Name:Yushen
Certification:CCC, ISO, CQC
Model Number:SLNC-075Y
Minimum Order Quantity:1 set
Delivery Time:1-2weeks
Payment Terms:T/T
Contact Now

Add to Cart

Active Member
Location: Shanghai Shanghai China
Address: Foreign sales office: 588 South Qilianshan Road ,Putuo area, Shanghai,China
Supplier`s last login times: within 27 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Silent Central Heating And Cooling System / High Speed Heat Pump Central Heating


Central Heating And Cooling System DESCRIPTION


Central Heating And Cooling System use electricity to capture heat and move it from one place to another. They don't generate heat.

Higher efficiency heat pump pool heaters usually use scroll compressors versus the reciprocal compressors of standard units.

Heat pump pool heaters work efficiently as long as the outside temperature remains above the 45ºF–50ºF range. The cooler the outside air they draw in, the more energy they use. However, since most people use outdoor swimming pools during warm and mild weather, this usually isn't an issue.


Heat Pump Cooling System Parameter


ModelSLNC-075Ycode name.pdf Central Heating And Cooling System
Compressor capacity25HP
FunctionHeating and Cooling
Electricity380V-3N-50Hz
Working conditions-25~+45
DataHeataNominal capacityKW44.5
Input powerKW18.3
COP/2.4
Heating IPLV(H)2.7
CoolbNominal capacityKW62
Input powerKW20.7
COP/3
Cooling IPLV(C)2.7
A7W35cKW/COP75.0/4.2
A2W35KW/COP62.5/3.20
A-7W35KW/COP50/2.9
A-15W55KW/COP45.5 /1.97
A-20W45KW/COP37.4/2.04
Max. running currencyA56
Compressor quantityset2
Refrigerant/charging quantity kg/R22/15*2
Air blow type/Top
Water pipe diametermm50
Rating flowm³/h12.6
Water side pressure losskPa≤45
Noise leveldB(A)62
Overall dimensions(L×W×H)mm2100×1100×2080
Weightkg730

A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃

a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal


Central Heating And Cooling System Advantages

  • Larger application range , yushen heat pump could be used from environmental temperature:-25℃ to +45 ℃ /or from -13℉ to 113 ℉
  • 100% finished products testing,quality Components such as Copeland compressor, Danfoss valves
  • 35% more powerful than other products,yushen air-source heat pump has longer heating time and shorter defrosting time
China Silent Central Heating And Cooling System / High Speed Heat Pump Central Heating supplier

Silent Central Heating And Cooling System / High Speed Heat Pump Central Heating

Inquiry Cart 0