Add to Cart
318 Y / H05VV F Insulated Electrical Wire Rubber Compound Type Class 5
APPLICATION
Ordinary duty flexible rubber cords suitable for use in domestic premises, such as kitchens and offices.
CONSTRUCTION
Conductor
Class 5 flexible copper conductor according to BS EN 60228 (previously BS 6360)
Insulation
Rubber compound type E14 according to BS EN 50363
Sheath
Rubber compound type EM3 according to BS EN 50363
CABLE STANDARDS
BS EN 50525-2-21, VDE0282 (BS 6500)
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the Sunwin Cables laboratory.
Cable performance in respect of conductor resistance, construction quality (workmanship),dimensional consistency, and other parameters are verified to published standardsand approved product drawings. Conformance to RoHS (Restriction of the use ofHazardous Substances) is determined and confirmed.
Voltage Rating (Uo/U) 300/500V
Temperature Rating
Flexed: -25°C to +60°C
Minimum Bending Radius Flexed: 4 x overall diameter Fixed: 3 x overall diameter
Sheath Colour
Black White
DIMENSIONS
Sunwin PART NO. | NO. OF CORES | NOMINAL CROSS SECTIONAL AREA mm² | NOMINAL THICKNESS OF INSULATION mm | NOMINAL OVERALL DIAMETER mm | NOMINAL WEIGHT kg/km |
A5H020075** | 2 | 0.75 | 0.6 | 6.1 | 53 |
A5H02010** | 2 | 1 | 0.6 | 6.6 | 64 |
A5H02015** | 2 | 1.5 | 0.8 | 7.8 | 95 |
A5H02025** | 2 | 2.5 | 0.9 | 9.2 | 140 |
A5H02040** | 2 | 4 | 1 | 10.8 | 180 |
A5H030075** | 3 | 0.75 | 0.6 | 6.6 | 65 |
A5H03010** | 3 | 1 | 0.6 | 7 | 77 |
A5H03015** | 3 | 1.5 | 0.8 | 8.4 | 115 |
A5H03025** | 3 | 2.5 | 0.9 | 9.9 | 170 |
A5H03040** | 3 | 4 | 1 | 11.7 | 240 |
A5H03060** | 3 | 6 | 1 | 13.3 | 320 |
A5H040075** | 4 | 0.75 | 0.6 | 7.3 | 80 |
A5H04010** | 4 | 1 | 0.6 | 7.6 | 95 |
A5H04015** | 4 | 1.5 | 0.8 | 9.4 | 145 |
A5H04025** | 4 | 2.5 | 0.9 | 11.1 | 210 |
A5H04040** | 4 | 4 | 1 | 13.0 | 300 |
A5H04060** | 4 | 6 | 1 | 14.5 | 405 |
A5H050075** | 5 | 0.75 | 0.6 | 8.1 | 100 |
A5H05010** | 5 | 1 | 0.6 | 8.4 | 115 |
A5H05015** | 5 | 1.5 | 0.8 | 10.3 | 170 |
A5H05025** | 5 | 2.5 | 0.9 | 12.4 | 255 |
A5H05040** | 5 | 4 | 1 | 14.5 | 355 |
* Sunwin Part No. shown above designate the sheath colour (*). For each colour substitute * for a colour code as listed below. e.g. A5H020075WH = 0.75mm2 White
Colour Codes
COLOUR | Black | White |
CODE | BK | WH |
CONDUCTORS
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA mm² | MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm | MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC |
Plain Wires ohms/km | ||
0.75 | 0.21 | 26 |
1 | 0.21 | 19.5 |
1.5 | 0.26 | 13.3 |
2.5 | 0.26 | 7.98 |
4 | 0.31 | 4.95 |
6 | 0.31 | 3.3 |
The above table is in accordance with BS EN 60228 (previously BS 6360)
ELECTRICAL CHARACTERISTICS
NOMINAL CROSS SECTIONAL AREA mm² | CURRENT CARRYING CAPACITY Amps | MAXIMUM MASS SUPPORTABLE BY TWIN FLEXIBLE CORD (See Regulations 522.7.2 and 559.6.1.5 from 17TH Edition of Wiring Regulations) kg | |
Single-Phase AC | Three-Phase AC | ||
0.75 | 6 | 6 | 3 |
1 | 10 | 10 | 5 |
1.5 | 16 | 16 | 5 |
2.5 | 25 | 20 | 5 |
4 | 32 | 25 | 5 |
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
Voltage Drop
NOMINAL CROSS SECTIONAL AREA mm² | DC OR SINGLE-PHASE AC mV/A/m | THREE-PHASE AC mV/A/m |
0.75 | 62 | 54 |
1 | 46 | 40 |
1.5 | 32 | 27 |
2.5 | 19 | 16 |
4 | 12 | 10 |
Conductor operating temperature: 60ºC
The above table is in accordance with Table 4F3B of the 17th Edition of IEE Wiring Regulations.
DE-RATING FACTORS
AIR TEMPERATURE | 35ºC | 40ºC | 45ºC | 50ºC | 55ºC |
DE-RATING FACTOR | 0.91 | 0.82 | 0.71 | 0.58 | 0.41 |
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.