Home /Transformers /

Precision Current Transformer Analyzer / Power Transformer Testing Equipment

Precision Current Transformer Analyzer / Power Transformer Testing Equipment

Brand Name:GFUVE
Certification:GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012
Model Number:GF106T
Minimum Order Quantity:1
Delivery Time:1-2week
Payment Terms:T/T, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Beijing Beijing China
Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Supplier`s last login times: within 37 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

CT PT Analyzer GF106T


Ct/Pt Analyzer/Instrument Transformer Testing/Ta/Tv Analyzer /Pt Test System


I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Withstand test of power frequency alternating current
5. Current Injecting5. Degauss
6. Degauss6. Calculation of knee point value
7. Withstand test of power frequency alternating current7. Actual secondary load test 
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test 
10. Resistance test 

PARAMETERS

Electrical parameters
Accuracy0.2%, 0.5%
Power supplyAC 220V±10% or AC 110V±10%, 50/60Hz
Excitation voltage output0-2500Vrms,
Excitation current output0-5Arms (20A peak-value)
Large current output0-1000A
Electrical parameters - continued
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurementRange0.1-300Ω
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurementAccuracy±4min
Resolution0.01min
CT ratio error measurementRange≤25000A/5A(5000A/1A)
Accuracy≤0.5%
PT ratio error measurementRange1-500KV
Accuracy≤0.5%
Standards 
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm)400 x 250 x 250
Weight (kg)≤22
Environmental conditions 
Relative humidity90RH%
Operating temperature-10°C to +40°C
Altitude≤1000m
China Precision Current Transformer Analyzer / Power Transformer Testing Equipment supplier

Precision Current Transformer Analyzer / Power Transformer Testing Equipment

Inquiry Cart 0