Home /Switching Power Supply /

GF302D Three Phase Meter Calibration Equipment Test Bench With Phantom Load Power Source

GF302D Three Phase Meter Calibration Equipment Test Bench With Phantom Load Power Source

Brand Name:GFUVE
Certification:CE,ISO9001:2008, IEC
Model Number:GF302D-100a
Minimum Order Quantity:1Set
Delivery Time:20days upon receipt of payment
Payment Terms:Western Union, T/T, L/C, D/A, D/P, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Location: Beijing Beijing China
Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Supplier`s last login times: within 37 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

GF302D GFUVE three phase portable energy meter test bench with phantom load power source


Application


The model GF302D portable energy meter test bench is used for grid corporation of measurement and energy test center, management department of power supply bureau, national energy measurement of testing authorities, and also used to test each kind of single/three phase kWh meter of industries and mining enterprises as well as electric meter manufacturers. Meanwhile, the calibrator also can be used as one high precision standard power source.


Portable Three Phase Energy Meter Testing Equipment. Energy Meter Test - Portable Meter Testing Equipment GF302D Portable Three Phase Energy Meter Testing Equipment. Overview: The GF302D Series Portable Three Phase Energy Meter Testing Equipment comprises of high-stability three phase program-controlled power source and three phase standard watt-hour meter.


Features

  • Min current output 1mA
  • Predefined multiple load points
  • Reference meter and power source integration
  • User friendly menu guided operation
  • Easy verification and analysis of meter installations
  • Automatic operation without need of an external PC
  • Generation of harmonics in current and voltage up to the 51th
  • Verification of the load conditions on metering installation
  • Verification of the energy registration
  • Automatic testing mechanical meter and electronic meter error
  • Voltage, current, frequency, phase angle, power factor, harmonics can be regulated
  • 1P2W, 1P3W, 3P3W, 3P4W can be set
  • 4 quadrant measurement
  • Vector diagram display and phase sequence indication on integrated colored screen
  • Especially configured USB stick for storage of customer data and measurement results

PARAMETERS


Electrical parameters 
Accuracy0.05%, 0.1%
Power SupplyOne Phase AC 180-265V, frequency 50/60Hz.
AC Voltage Output 
Range(U1,U2,U3)57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range(0-120)%RG(1)
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability0.01%/120s
Distortion0.3% (Non-capacitive load)
Output loadeach phase 25VA
Measuring accuracy0.05%RG
AC Current Output 
Range(I1,I2,I3)200mA, 1A, 5A, 20A, 100A
Adjustment range(0-120)%RG
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability<0.01%/120s
Distortion≤0.3% (Non-capacitive load)
Output load45VA
Accuracy0.05%RG
Power Output 
Active power output stability<0.01%RG/120s
Reactive power output stability<0.02%RG/120s
Active power measuring accuracy0.05%RG
Reactive power measuring accuracy0.1%RG
Phase Output 
Output adjustment range0°-359.999°
Output adjustment fineness10, 1, 0.1, 0.01 as optional.
Resolution0.01°
Accuracy0.05°
Power Factor 
Adjustment range-1 ~ 0 ~ 1
Resolution0.0001
Measurement accuracy0. 0005
Frequency Output 
Adjustment range45Hz-65Hz
Output adjustment fineness5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution0.001Hz
Accuracy0.005Hz
Voltage /Current/Harmonic Setting 
Harmonic number2-51times
Harmonic content0-40%
Harmonic phase0-359.99
Harmonic setting accuracy(10%±0.1%)RD(2)
Power Energy Measurement Error 
Active power energy0.05%RG
Reactive power energy0.1%RG
Power Pulse Output 
Power pulse typeactive pulse, reactive pulse
Active power pulse output5V, 10mA
Power Pulse Input 
Energy pulse typesupport active and reactive pulse, the highest frequency power pulse input is 180K.
Mechanical parameters 
Dimensions (W×D×H) (mm)500x600x175
Weight (kg)About 27
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.

Photo

China GF302D Three Phase Meter Calibration Equipment Test Bench With Phantom Load Power Source supplier

GF302D Three Phase Meter Calibration Equipment Test Bench With Phantom Load Power Source

Inquiry Cart 0