Product Details

TEST-330 Portable Three Phase Protection Relay Test System With instruments testing function


The Test-330 Portable Three Phase Protection Relay Test System is the first choice for applications requiring very high accuracy more than 0.1%. This unit is not only an excellent test set for protection devices of all kinds but also a universal calibrator. It can as a ac or dc current source and voltage, 0-10A, 0-130V accuracy 0.1%.

Its unique accuracy and reliability make the Test-330 ideal for protection and measurement equipment manufacturers for research and development, production and electric power company type testing.


TEST-330 is the new economic version of relay test equipment TEST-330. This relay test kit is with 3*30A and 5*130V, only 16.6kg with powerful Powertest software,it can test most types of modern multi-function relays. TEST-330 is the best portable and economic choice for relay test engineers who travel a lot. and then it can Independent work without PC software.


The TEST-330 is a multipurpose, light-weight, field portable test set capable of testing a wide variety of electro-mechanical, solid state and microprocessor-based protective relays, motor overload relays, and similar protective devices.

The unit can be operated either manually via the built-in Keyword, or placed under full computer control via the GFUVE, Advanced Visual Testing Software, or the GFUVE-software running on a PC. In addition, with the open communication architecture, the unit can also be used with third-party software programs such as National Instruments LabVIEW™.


FEATURES


  • Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
  • Eight-path synchronous D/A output in a single machine
  • High-accuracy linear power amplifier
  • Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
  • Intelligent self-protection function
  • Plentiful Binary and powerful software function
  • Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
  • Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V
  • This model relay test equipment is designed with 3 currents (3*40A) and 3 voltages (3*300V).
    The local software system is designed based on Windows sytstem, which is easy and conveninent for operation and upgrade. It supports using templates for various relay testings, for example, G59.
    It is the favorable and conomical testing solution for commissioning work in distribution grid.Integrated Smart Touch View Interface.
  • Multi-colored graphics with intuitive navigation
  • Stand-alone operation, no PC required to operate
  • High current output - 90 Amps at 520 VA per phase
  • Flexible output design provides up to 10a currents
  • Dynamic, Transient and GPS Satellite Synchronized End-to- End Testing Capability

OVERVIEW

  • 3 phase current output
  • 5 phase voltage output
  • 8 binary input, 4 binary output
  • Accuracy more than 0.1%

TEST ITEM


  • Distance protection
  • Zero sequence protection
  • Setting group test
  • State sequence
  • Synchronization test
  • Special test
  • Oscillation test
  • Metering instrument
  • Hardware checkout
  • Low Voltage protection
  • Fault Waveform Reproduction
  • U/I test
  • DC test
  • Impedance characteristics
  • Power direction test
  • I-T test
  • Differential relay
  • Harmonic test
  • Differential protection

PARAMETERS


Electrical parameters
Power voltageAC220V±10% or AC110V±10%, 50/60Hz±10%
Time measurement0.1ms-999999.999s
AC current output 
Phase current output (effective value)3 x 0-30A
Maximum power output260VA/phase
Maximum parallel current output (effective value)0-90A
Long-term allowable working value of phase current
(effective value)
>10A
Allowable working time of maximum current>11s
Accuracy class<±0.1%
AC voltage output 
Phase voltage output (effective value)5 x 0-130V
Line voltage output (effective value)0-260V
Maximum power output70VA/phase
Accuracy class<±0.1%
DC current output 
Output range-10 to 10A or 3 x 0 to ±10A
Maximum power output200VA
Accuracy class<±0.1%
DC voltage output 
Output range0-300V or 5 x 0 to ±130V
Maximum output power130VA
Accuracy class<±0.1%
Binary input 
Idle contact1-20mA, 24V (DC)
Electric potential contact250V/0.5A (DC)
Binary output 
Idle contact250V/0.5A (DC)
Rated output 
Frequency error<±0.01Hz
Phase error<±0.1%
Waveform distortion<±0.3% (fundamental wave)
Time error<40µs
Output frequency0-1050Hz
Superposed harmonic wave0-21times
Mechanical parameters 
Dimensions (L×W×H) (mm)360x195x375
Weight (kg)16.6
Environmental conditions
Use range0°C to 45°C
Storage range-25°C to 70°C

Photo