Home /Relays /

Intelligent K2063i Protection Relay Testing Support Goose

Intelligent K2063i Protection Relay Testing Support Goose

Brand Name:Kingsine
Certification:CE/ISO9001
Model Number:K2063i
Minimum Order Quantity:1 set
Delivery Time:15 working days
Payment Terms:L/C,T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong
Address: 6/F, Block 4-CD, TianAn Cyber Park, Futian District, Shenzhen 518048,.China
Supplier`s last login times: within 1 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Intelligent K2063i Protection Relay Testing Support Goose


Description Of Differential Protection Relay Test Set

Relay protection microcomputer test device plays a key role in operating electricity power systems reliably and safely. It is the testing device used in professional field of microcomputer protection, relay protection, excitation measurement, fault recorder.


Feature Of IEC61850 Protection Relay Test

Universal Relay Test Applications
Inbuilt 9.7” True color TFT LCD with touch screen, numerical and shortcut keyboard, fully control with / without laptop
10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics.
Variable battery simulator, DC 0-350V, 140Watts max.
Transient play back up to 3KHz
Fully function KRT software testing modules
Graphical test modules and templates for testing of various relays
Quick relay testing facility in Manual mode

Specification Of Secondary Injection Test Kit

Voltage Outputs
Output Range & Power4×310 V ac (L-N)124 VA max each
3×350 V dc (L-N)140 W max each
Accuracy±2mV @ <2V ac
<0.015%Rd+0.005Rg Typ. @ 2~310V ac
<0.04%Rd+0.01Rg Guar. @ 2~310V ac
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage RangeRange I : 30V
Range II : 310V
Automatic Range
DC Offset<10mV Typ./ <60mV Guar
Resolution1mV
Distortion<0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power6×35A ac (L-N)450 VA max each
3×70A ac (2L-N)850 VA max each
1×100A ac (6L-N)1200 VA max
3×20A dc (L-N)300W max each
Accuracy±1mA @ <0.5A ac
<0.02%Rd+0.01Rg Typ. @ 0.5A~35A ac
<0.05%Rd+0.02Rg Guar. @ 0.5A~35A ac
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current RangeRange I: 3A
Range II: 35A
Automatic Range
DC Offset<3mA Typ./ <10mA Guar
Resolution1mA
Distortion<0.025%Typ. / <0.07% Guar.
Frequency & Phase Angle
Frequency RangeDC~1KHz, 3KHz transient
Frequency Accuracy±0.5ppm
Frequency Resolution0.001 Hz
Phase Range-360°~360°
Phase Accuracy<0.02° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution0.001°
Aux. DC Voltage Source (Battery simulator)
Range0~350V @ 140W max
Accuracy0.5%Rg Guar.

Advantage Of Secondary Current Injection Test Set

Powerful 6-phase relay test set and commissioning tool, convenient for field test;
6x35A & 4x310V high accuracy analog channels output;
9.7” True color TFT LCD, touch screen and keyboard operating, w/wo laptop control;
The ever-expanding test library templates


FAQ

Q: Can the relay protection tester show the impedance curve?

A: Yes.

Q: What is your technical advantages?

A: Our products with powerful 6-phase relay test set and commissioning tool, convenient for field test,6x35A & 4x310V high accuracy analog channels output.

Q: How long is the warranty period?

A: 3-Years guarantee of free repair and life-long maintenance

China Intelligent K2063i Protection Relay Testing Support Goose supplier

Intelligent K2063i Protection Relay Testing Support Goose

Inquiry Cart 0