Home /Heat Pump Water Heaters /

Geothermal ground water source heat pump with cooling

Geothermal ground water source heat pump with cooling

Brand Name:HISEER
Certification:CE, EN14511
Model Number:GHP20/B-DNNNE
Minimum Order Quantity:2 pieces
Delivery Time:15-20 days after TT payment
Payment Terms:TT or L/C at sight
Contact Now

Add to Cart

Active Member
Location: Guangzhou Guangdong
Address: Xicheng Industry Zone, Renhe Town, Baiyun District, Guangzhou, Guangdong, China
Supplier`s last login times: within 29 hours
Shipping
lt's easy to get a shipping quote! Just click the button below and complete the short form.
Get Shipping Quote
Product Details Company Profile
Product Details

Geothermal ground water source heat pump with cooling

Heat contained in earth, is called geothermal heat is usually used indirectly. Heat pumps taking heat from the ground are called “ground-water“. Heat is extracted using an underground collector. A heat carrying liquid is pumped through these pipes connected to the heat pump evaporator. The heat carrying liquid is non-freezing and ecologically harmless. Circulating liquid is cooled down in the heat pump evaporator and it is re-warmed in the underground collector by means of geothermal hea


GHP20/B-DNNNE, designed and tested by European standard EN14511, approved and tested by TUV china branch. Characterized by its high COP, competitive price and perfect quality.


HISEER geothermal ground source heat pump adopts the following world famous parts:

  • Siemens controller
  • SWEP or GEA plate type heat exchanger
  • Daikin compressor
  • Schneider A/C contactor
  • Emersion expansion valve
  • Emersion dry filter
  • Honeywell R410a refrigeration

HISEER GHP20/B-DNNNE, ground source heat pump, works by using heat stored in the ground from the sun's solar radiation to supply all of the energy required for a home's heating and hot water system.


How it works
There are three important elements to a ground source heat pump:

1.The ground loop
This is comprised of lengths of pipe buried in the ground, either in a borehole or a horizontal trench. The pipe is usually a closed circuit and is filled with a mixture of water and antifreeze, which is pumped around the pipe absorbing heat from the ground. The ground loop can be:
•Vertical, for use in boreholes
•Horizontal, for use in trenches
•Pound/Lake installation

2.A heat pump
In the same way that your fridge uses refrigerant to extract heat from the inside, keeping a ground source heat pump extracts heat from the ground, and uses it to heat your home.

3.Heat distribution system
This consists of under floor heating or radiators for space heating and in some cases water storage for hot water supply.


ADVANTAGES:

  • Suitable for the coldest winter area
  • The most high efficiency heat pump
  • Maintenance free
  • Indoor side installation
  • No noise level to disturb your neighbor

  • Reducing your carbon emission
  • Enjoying your green life by installing HISEER heat pumps
  • Reducing your heating and cooling bill with high efficiency HISEER heat pumps

GHP20/B-DNNNE technical data


Heat pump

Type

GHP20/B-DNNNE

Dimensions, weights, connection dimensions

 

 

Dimensions

HxWxD

960x600X600

Weight

kg

165

Refrigerant

Type

R410A

Filling weight

kg

3.4

Permissible operating pressure

Mpa

4.2

Pipe connector-hot side

Inch

G11/2”

Pipe connector-cold side

Inch

G11/2”

Evaporator

Type

Brazed plate heat exchanger

Condenser

Type

Compressor

 

1xScroll

Performance Heat pump

 

 

 

Heat output

at B0/W35

kW

20.3

Power consumption

kW

4.60

Performance factor

 

4.41

Hot side volume flow

m3/h

3.49

Cold side volume flow

m3/h

4.50

Heat output

at W10/W35

kW

25.7

Power consumption

kW

4.68

Performance factor

 

5.49

Hot side volume flow

m3/h

4.42

Cold side volume flow

m3/h

6.03

Cool output

at W35/W7

kW

21.80

Power consumption

kW

4.50

Performance factor

 

4.84

Inside volume flow

m3/h

3.75

Outside volume flow

m3/h

4.52

Power

Type

Triple phase with Hitachi compressor

Sound power level

dB(A)

48

The above data is tested by EN14511

China Geothermal ground water source heat pump with cooling supplier

Geothermal ground water source heat pump with cooling

Inquiry Cart 0